Vermont Casting LHERDV30 사용자 설명서

다운로드
페이지 32
18
10004894
LHEDV Series Direct Vent Insert
Gas Supply On
Supply Line Hooked Up
Shutoff Valve Open
NO
NO
NO
NO
Lockout Has Engaged. Wait 
60 Seconds And Try Again.
For Spark At Electrode While 
Depressing Piezo — 1/8" Gap To 
Pilot Hood Needed.
All Wiring Connections
Replace Piezo Ignitor
For Air In The Lines
Thermopile Needs A Minimum 
325mv. Adjust Pilot Flame Height.
All Wiring Connections.
Replace Thermopile
Thermocouple Needs A Minimum 
of 14mv.
Defective Valve. Turn To Pilot, 
Meter Should Read Greater Than 
100 Mv. If Not, Replace. 
Pilot Lights With 
Piezo Ignitor
YES
YES
YES
YES
Pilot Stays Lit
Pilot Lights Main 
Burner
System OK.
START
CHECK
Valve Is Turned On
On/off Switch Is Not Turned On. 
Watch For Grounded Wires!
Thermopile Needs A Minimum 
325mv.
Plugged Burner Orifice.
FP396
NVC-standing pilot troubleshooting
11/22/96
Troubleshooting the Gas Control System
Honeywell Millivolt Valve