General Information for Connecting Vent Pipes
Crimped End Pipes
Before joining elbows and pipes, apply a bead of high
temperature sealant to the crimped end of the elbow or
pipe.
Join the pipes using a 2” (50 mm) overlap and secure
the joints with three sheet metal screws (Fig. 13). Wipe
off excess sealant.
Canadian Installations:
The venting system must be installed in accordance
with the current CSA-B149.1  installation code.
USA Installations:
The venting system must conform to local codes and/
or the current National Fuel Code ANSI Z223.1.
Only venting components manufactured by Vermont
Castings, Majestic Products may be used in Direct
Vent systems.
1" (25 mm) from 
crimped end of pipe
Screw 
CFM175
Fig. 13   Apply a bead of high temperature sealant.
Outside Corner
Inside Corner
Termination Clearances
Termination clearances for buildings with combustible and noncombustible exteriors. 
A =
Combustible 
  6"(152mm)
Noncombustible 
  2"(50mm)
B =
Combustible 
  6"(152mm)
Noncombustible 
  2"(50mm)
A
Balcony - 
with no side wall
G = 
Combustible
NonCombustible
  12"(305mm)
  
G
Balcony - 
with perpendicular side wall
H = 24"(610mm)
J = 20"(508mm)
      
H
J
B
Recessed Location
C = Maximum depth of 48"
       (1219mm) for recessed 
       location.
       
D = Minimum width for back wall 
       of a recessed location.
       Combustible 38"(965mm)
       Noncombustible 24"(610mm)
E = Clearance from corner in 
       recessed location.
       Combustible 6"(152mm)
       Noncombustible 2"(50mm)
C
D
C
E
V
V
Combustible &
NonCombustible
V
V
V
CFM115
Fig. 12  Termination clearances.