Y8150 FRESH AIR VENTILATION SYSTEM, W8150 FRESH AIR VENTILATION CONTROL
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN  55422
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Toronto, Ontario  M1V 4Z9
customer.honeywell.com
® U.S. Registered Trademark
© 2011 Honeywell International Inc.
68-0282—07  T.D.  Rev. 02-11 
Printed in U.S.A.
Fig. 10. Wiring fan for a steam humidifier.
Multi-System Setup Example
Total square feet and bedrooms should be proportionately 
split between the ventilation controls based on sq ft served by 
each system regardless of where the bedrooms are located.
Example: 5,000 sq ft, six bedrooms:
System 1: 
• serves 3200 sq ft, 
• two bedrooms. 
• fresh air intake measured at 127 cfm.
System 2: 
• serves 1800 sq ft, 
• four bedrooms
• fresh air intake measured at 98 cfm.
Set W8150 for System 1:
• 3100 sq ft,
• four bedrooms
• 130 cfm.
Set W8150 for System 2: 
• 1900 sq ft, 
• two bedrooms
• 100  cfm.
CONVERSION TABLE
Wake
Room
System
Fan
Heat
Auto
AM
DST
Tue
W
1
C
R
W
2
Y
1
Y
2
G
W
1
C
R
C
R
W
2
Y
1
Y
2
G
M22021A
G
F
R
C
C
C
C
H
W
G
T
HVAC
W8150A
HE440
FAN
R8222
BLACK
BLUE
BLUE
RED
Area
Airflow
sq ft
sq m
cfm
lps
1000
93
40
19
1300
121
50
24
1600
149
60
28
1900
177
70
33
2200
204
80
38
2500
232
90
42
2800
260
100
47
3100
288
110
52
3400
316
120
57
3700
344
130
61
4000
372
140
66
4300
399
150
71
4600
427
160
76
Airflow
cfm
6 in. duct
(15.2 cm)
7 in. duct
(17.8 cm)
fpm
ms
fpm
ms
40
204
1.0
150
0.8
50
255
1.3
187
1.0
60
306
1.6
225
1.1
70
357
1.8
262
1.3
80
407
2.1
299
1.5
90
458
2.3
337
1.7
100
509
2.6
374
1.9
110
560
2.8
412
2.1
120
611
3.1
449
2.3
130
662
3.4
486
2.5
140
713
3.6
524
2.7
150
764
3.9
561
2.9
160
815
4.1
599
3.0