A p p e n d i x     l    
I - 1
C o n t r o l   S e t u p
1/32 DIN Watlow SD controller Setup Sheet
Enter the following parameters
Menu
Parameter
Description
Setting
Set Up Page
Sen
Input sensor type
RTD
up & down for C-F
Temperature Units (degrees)
F
3 seconds
S.dec
Temperature Decimal Places
0
IS.en
Infosense
no
SP.Lo
Set Point Low Limit
40.0
SP.hi
Set Poing High Limit
65
Ftr.e
Input Filter
Both
Flt.r
Filter value - Seconds
5
Ot1
Output 1 function
heat
Ctr1
Control Method 1
ftb
Ftb1
Cycle time 1
10
PL 1
Power Limit 1
100%
PSL1
Output Power Limit Sacle Low 1
0%
PSH1
Output Power Limit Sacle High 1
90%
nLF1
Output Non-Linear Function 1
Off
Ot2
Output 2 Function - SP devaition
dE.AL
hys2
Alarm Hysteresis 2 
1.5F
Lgc2
Alarm relay state on alarm - open
Al o
Lat2
Alarm 2 latching
nLat
dSP2
Alarm 2 Message
on
ACLF
AC line frequency
60
Unit
Units of Measurement
SI
I.Err
Input error latching
nLat
FAIL
Input Error Failure Mode
bPLS
Man
Manual Error Level
0%
dSP
Active Displays
nor
rP
Ramping Mode
off
LOC
Security Lockout
3
Programming
Adv and INF keys 6 seconds
P1
Temperature Units - C-F
F
P2
Low Temp Dev. alarm - A2.Lo
-4
P3
High Temp dev Alarm - A2.HI
20
P4 
Proportional Band Hot Gas - pb.ht
3
P5
Intergral Hot Gas  - It.ht
3.4
P6
Derivative - dE.ht
0.1