Carrier 17/19EX 사용자 설명서
![Carrier](https://files.manualsbrain.com/attachments/a5814427f7c9329002f659367a985e4e90a2f895/common/fit/150/50/bb73826c02c94f2dc69e4b713d56e91a36006746df7aaf5261854985b326/brand_logo.png)
Before Initial Start-Up
Job Data Required
•
list of applicable design temperatures and pressures (product data submittal)
•
machine certified drawings
•
starting equipment details and wiring diagrams
•
diagrams and instructions for special controls or options
•
17/19EX Installation Instructions
•
pumpout unit instructions
Equipment Required
•
mechanic’s tools (refrigeration)
•
digital volt-ohmmeter (DVM)
•
clamp-on ammeter
•
electronic leak detector
•
absolute pressure manometer or wet-bulb vacuum indicator (
•
500 v insulation tester (megohmmeter) for compressor motors with nameplate volt-
age of 600 v or less, or a 5000-v insulation tester for compressor motor rated above
600 v
age of 600 v or less, or a 5000-v insulation tester for compressor motor rated above
600 v
Using the Utility Vessel and Pumpout System
section for: pumpout system
preparation, refrigerant transfer, and machine evacuation.