SNMP Trap 
Numbers
1151
Event ID — 2173
Description
Unsupported configuration detected. The SCSI rates of the enclosure management 
modules (EMMs) are not the same. EMM 0 % 1 EMM 1 % 2
Severity
Warning / Non-critical
Cause and 
Action
Cause: An unsupported configuration was detected.
Action: Replace one of the EMMs with the matching SCSI rate EMM.
Related Alert 
Information
Clear Alert Number: None
Related Alert Number: None
Local Response Agent (LRA) Number: 2090
SNMP Trap 
Numbers
853
Event ID — 2174
Description
The controller battery has been removed.
Severity
Warning / Non-critical
Cause and 
Action
Cause: The controller cannot communicate with the battery. The battery may be 
removed, or the contact point between the controller and the battery may be burnt 
or corroded.
Action: Replace the battery if it has been removed. If the contact point between 
the battery and the controller is burnt or corroded, you must replace either the 
battery or the controller, or both. See the hardware documentation for information 
on how to safely access, remove, and replace the battery.
Related Alert 
Information
Clear Alert Number: None
Related Alert Number: 2188, 2318
Local Response Agent (LRA) Number: 2100
SNMP Trap 
Numbers
1153
Event ID — 2175
Description
The controller battery has been replaced.
Severity
OK / Normal / Informational
Cause and 
Action
Cause: This alert is for informational purposes.
Action: None