Environmental specifications
Relative humidity
Storage
5% to 95% RH with 33°C (91°F) maximum dew 
point. Atmosphere must be non-condensing at all 
times.
Operating
10% to 80% Relative Humidity with 29°C (84.2°F) 
maximum dew point.
Maximum vibration
Operating
0.26 G
rms
 at 5 Hz to 350 Hz (all operation 
orientations).
Storage
1.88 G
rms
 at 10 Hz to 500 Hz for 15 min (all six 
sides tested).
Maximum shock
Operating
Six consecutively executed shock pulses in the 
positive and negative x, y, and z axes of 40 G for 
up to 2.3 ms.
Storage
Six consecutively executed shock pulses in the 
positive and negative x, y, and z axes (one pulse 
on each side of the system) of 71 G for up to 2 
ms.
Maximum altitude
Operating
3048 m (10,000 ft).
Storage
12,000 m (39,370 ft).
Operating temperature de-rating
Up to 35 °C (95 °F)
Maximum temperature is reduced by 1°C/300 m 
(1°F/547 ft) above 950 m (3,117 ft).
35 °C to 40 °C (95 °F to 104 °F)
Maximum temperature is reduced by 1°C/175 m 
(1°F/319 ft) above 950 m (3,117 ft).
40 °C to 45 °C (104 °F to 113 °F)
Maximum temperature is reduced by 1°C/125 m 
(1°F/228 ft) above 950 m (3,117 ft).
Particulate contamination
NOTE: This section defines the limits to help avoid IT equipment damage and/or failure from 
particulates and gaseous contamination. If it is determined that levels of particulates or gaseous 
pollution are beyond the limits specified below and are the reason for the damage and/or failures 
to your equipment, it may be necessary for you to re-mediate the environmental conditions that 
are causing the damage and/or failures. Re-mediation of environmental conditions will be the 
responsibility of the customer.
Air filtration
Data center air filtration as defined by ISO Class 8 
per ISO 14644-1 with a 95% upper confidence 
limit.
109