Functions 
 
3.3 Basic functions / parameters 
M200D AS-Interface Basic 
Manual, 03/2009, A5E01668085-01 
21
 
3.3 
Basic functions / parameters 
Definition 
Basic parameters are "central" parameters required by a range of device functions.  
3.3.1 
Rated operating current 
Here, you can enter the rated operating current that the branch (switchgear and motor) can 
carry without interruption. This is usually the rated motor current. The setting range depends 
on the output class of the M200D motor starter (0.15 ... 2 A or 1.5 ... 12 A). 
 
NOTICE 
 
The rated operating current is one of the key parameters. 
The rated operating current must always be set if motor protection is to be ensured via the 
electronic overload relay.   
The overload relay can be deactivated. 
In this case, motor protection must be ensured by means of a thermistor in the motor. 
 
Notes 
●  On the motor starter, the default rated operating current is set to the minimum value. 
●  The rated operating current for the M200D AS-i Basic motor starter is set by means of the 
rotary coding switch. For more information, see Parameterization via local setting 
(Page 72). 
 
3.3.2 
Protection against voltage failure 
If the supply voltage fails, the last overload message "Overload" is retained.