Functions 
 
3.6 Motor protection 
 
M200D AS-Interface Basic 
28
 
Manual, 03/2009, A5E01668085-01 
Motor protection shutdown response   
You can use this parameter to determine how the motor starter is to respond to a 
temperature sensor or thermal motor model overload: 
●  Shutdown without restart (AUTO RESET = off) 
●  Shutdown with restart (AUTO RESET = on) 
 
WARNING 
 
Motor restarts automatically if AUTO RESET is on. 
Can Cause Death, Serious Injury, or Property Damage 
The motor starter restarts automatically after the recovery time if a start command is 
present (autoreset). (autoreset). 
Make sure that you take appropriate measures to exclude the risk of hazardous conditions. 
 
 
Temperature sensor monitoring   
Temperature sensor monitoring is activated when a PTC type A temperature sensor is 
parameterized. 
This device parameter monitors the temperature sensor cable for interruptions (wire 
breakage) and short-circuits. The motor is shut down if either of these scenarios occurs. 
Settings 
The possible settings for the M200D AS-i Basic motor starter can be found in section