Siemens M200D 사용자 설명서
Functions
3.6 Motor protection
M200D AS-Interface Basic
28
Manual, 03/2009, A5E01668085-01
Motor protection shutdown response
You can use this parameter to determine how the motor starter is to respond to a
temperature sensor or thermal motor model overload:
● Shutdown without restart (AUTO RESET = off)
● Shutdown with restart (AUTO RESET = on)
● Shutdown without restart (AUTO RESET = off)
● Shutdown with restart (AUTO RESET = on)
WARNING
Motor restarts automatically if AUTO RESET is on.
Can Cause Death, Serious Injury, or Property Damage
The motor starter restarts automatically after the recovery time if a start command is
The motor starter restarts automatically after the recovery time if a start command is
present (autoreset). (autoreset).
Make sure that you take appropriate measures to exclude the risk of hazardous conditions.
Temperature sensor monitoring
Temperature sensor monitoring is activated when a PTC type A temperature sensor is
parameterized.
This device parameter monitors the temperature sensor cable for interruptions (wire
This device parameter monitors the temperature sensor cable for interruptions (wire
breakage) and short-circuits. The motor is shut down if either of these scenarios occurs.
Settings
The possible settings for the M200D AS-i Basic motor starter can be found in section