Functions 
 
3.12 Solid-state/mechanical switching technology 
 
M200D AS-Interface Basic 
42
 
Manual, 03/2009, A5E01668085-01 
3.12 
Solid-state/mechanical switching technology 
Solid-state switching  
The motor starter controls the motor (two phases) with thyristors. Phase L1 is not switched 
but is instead looped through from the 400 V power connection to the motor connection via 
the integrated disconnecting means. 
 
DANGER 
 
Hazardous voltage 
Can cause death or serious injury. 
If the line voltage is present at the 400 V power connection of the motor starter, hazardous 
voltage may still be present at the motor starter output even if a start command has not 
been issued. 
When carrying out any work on the branch, make sure that you disconnect it via the 
disconnecting means. 
 
Mechanical switching 
The motor starter controls the motor (three phases) with contactors. 
On device versions with a rated operating current of 0.15 - 2A (3RK13..-6KS41) RC 
elements are integrated on the motor output side to dampen interference pulses. 
Contact block defective 
If a contact block is defective (contactor welded / thyristor failure), the motor starter cannot 
shut down the motor. 
If necessary, evaluate the message "Device fault" and shut down the branch on the basis of 
this by means of an upstream contact block.