Installation / connection 
 
4.1 Installation 
 
M200D AS-Interface Basic 
54
 
Manual, 03/2009, A5E01668085-01 
Offlline addressing with the addressing unit   
The motor starter is addressed via the AS-i connection socket. 
 
 
Note 
When assigning the address via the addressing unit, unscrew the encoders (sensors) from 
the digital inputs to prevent the addressing unit from being overloaded by their power 
consumption. 
If the older version of the addressing unit (3RK1904-2AB00) is used, a special addressing 
cable (3RK1901-3RA00) is required to connect the module to the addressing unit. 
 
 
 




ASI+
ASI-
4 1
3 2
1.  Connect the motor starter to the addressing unit (3RK1904-2AB01) using a standard M12 
connection cable (2 or 3 pin) (e.g. 3RX8000-0GF32-1AB5). 
(4 or 5-pin connection cables must not be used for addressing purposes.) 
2.  Assign an address to the module. 
• 
Set the selector switch to ADDR. 
• 
Press 
. The address of the connected module is read and displayed. 
• 
Select the address by choosing 
• 
To transfer the address to the module, choose 
3.  Unplug the addressing cable and reconnect the motor starter using the AS-i cable. 
Online addressing with the AS-i master and in the PLC configuration software 
For instructions on how to address the motor starter using the AS-i master or in the 
configuration software, refer to the manual for the AS-i master you are using.