Installation / connection
4.1 Installation
M200D AS-Interface Basic
54
Manual, 03/2009, A5E01668085-01
Offlline addressing with the addressing unit
The motor starter is addressed via the AS-i connection socket.
Note
When assigning the address via the addressing unit, unscrew the encoders (sensors) from
When assigning the address via the addressing unit, unscrew the encoders (sensors) from
the digital inputs to prevent the addressing unit from being overloaded by their power
consumption.
If the older version of the addressing unit (3RK1904-2AB00) is used, a special addressing
If the older version of the addressing unit (3RK1904-2AB00) is used, a special addressing
cable (3RK1901-3RA00) is required to connect the module to the addressing unit.
ASI+
ASI-
4 1
3 2
1. Connect the motor starter to the addressing unit (3RK1904-2AB01) using a standard M12
connection cable (2 or 3 pin) (e.g. 3RX8000-0GF32-1AB5).
(4 or 5-pin connection cables must not be used for addressing purposes.)
2. Assign an address to the module.
•
Set the selector switch to ADDR.
•
Press
. The address of the connected module is read and displayed.
•
Select the address by choosing
.
•
To transfer the address to the module, choose
.
3. Unplug the addressing cable and reconnect the motor starter using the AS-i cable.
Online addressing with the AS-i master and in the PLC configuration software
For instructions on how to address the motor starter using the AS-i master or in the
configuration software, refer to the manual for the AS-i master you are using.