Schneider Electric Altivar 12 사용자 설명서
BBV28581 05/2010
95
Code
Name/Description
Adjustment range
Factory setting
FLt-
Fault detection management menu
(continued)
USb-
Undervoltage menu
USb
M Undervoltage fault management
0
O
1
1
Behavior of the drive in the event of an undervoltage
v
Detected fault and R1 relay open.
v
Detected fault and R1 relay closed.
StP
M Undervoltage prevention
nO
nO
rMP
Behavior in the event of the undervoltage fault prevention level being reached
v
No action (freewheel)
v
.
StM
T
M Undervoltage ramp deceleration time
0.0 to 10.0 s
1.0 s
=
FLt-
Fault detection management menu
(continued)
Strt
M IGBT test
nO
nO
YES
v
No test
v
The IGBTs are tested on power up and every time a run command is sent. These tests cause a slight
delay (a few ms). In the event of a fault, the drive will lock. The following faults can be detected:
delay (a few ms). In the event of a fault, the drive will lock. The following faults can be detected:
- Drive output short-circuit (terminals U-V-W): SCF display
- IGBT: xtF, where x indicates the number of the IGBT concerned
- IGBT: xtF, where x indicates the number of the IGBT concerned
IGBT short-circuited: x2F, where x indicates the number of the IGBT concerned
LFL1
M 4-20 mA loss behavior
nO
nO
YES
v
Fault ignored. This configuration is the only one possible if
.
v
Freewheel stop.
InH
M Detected fault inhibition assignment
nO
nO
L1H
L2H
L3H
L4H
L2H
L3H
L4H
To assign fault inhibit, press and hold down the “ENT” key for 2 s.
v
Function inactive
v
L1h:
LI1 active high
v
L2h:
LI2 active high
v
L3h:
LI3 active high
v
L4h:
LI4 active high
Following detected faults can be inhibited:
InFb
,
SOF
,
tnF
,
OHF
,
OLF
,
OPF1
,
OPF2
,
OSF
,
SLF1
,
SLF2
,
SLF3
,
tJF
, and
USF
.
DANGER
LOSS OF PERSONNEL AND EQUIPMENT PROTECTION
Enabling the fault inhibition parameter
InH
will disable the drive controller protection features.
•
InH
should not be enabled for typical applications of this equipment.
•
InH
should be enabled only in extraordinary situations where a thorough risk analysis demonstrates that the
presence of adjustable speed drive protection poses a greater risk than personnel injury or equipment damage.
Failure to follow these instructions will result in death or serious injury.
To change the assignment of this parameter press the “ENT” key for 2 s.
T
Parameter that can be modified during operation or when stopped.
I-O-
drC-
CtL-
FUN-
FLt-
COM-
2 s
2 s