Code
Name/Description
Adjustment range
Factory setting
FLt-
Fault detection management menu 
(continued)
USb-
Undervoltage menu
USb
Undervoltage fault management
0
O
1
Behavior of the drive in the event of an undervoltage
v
Detected fault and R1 relay open.
v
Detected fault and R1 relay closed.
StP
Undervoltage prevention
nO
nO
rMP
Behavior in the event of the undervoltage fault prevention level being reached
v
No action (freewheel)
v
Stop following an adjustable ramp 
.
StM
T
Undervoltage ramp deceleration time
0.0 to 10.0 s
1.0 s
Ramp time if 
 = 
FLt-
Fault detection management menu 
(continued)
Strt
IGBT test
nO
nO
YES
v
No test
v
The IGBTs are tested on power up and every time a run command is sent. These tests cause a slight 
delay (a few ms). In the event of a fault, the drive will lock. The following faults can be detected:
- Drive output short-circuit (terminals U-V-W): SCF display
- IGBT: xtF, where x indicates the number of the IGBT concerned
IGBT short-circuited: x2F, where x indicates the number of the IGBT concerned
LFL1
4-20 mA loss behavior
nO
nO
YES
v
Fault ignored. This configuration is the only one possible if 
 is not greater than 3 mA or if 
.
v
Freewheel stop.
InH
Detected fault inhibition assignment
nO
nO
L1H
L2H
L3H
L4H
To assign fault inhibit, press and hold down the “ENT” key for 2 s.
v
Function inactive
v
L1h:
 LI1 active high
v
L2h:
 LI2 active high
v
L3h:
 LI3 active high
v
L4h:
 LI4 active high
Following detected faults can be inhibited:
InFb
SOF
tnF
,
OHF
OLF
OPF1
OPF2
OSF
SLF1
SLF2
SLF3
tJF
, and 
USF
.
DANGER
LOSS OF PERSONNEL AND EQUIPMENT PROTECTION
Enabling the fault inhibition parameter 
InH
 will disable the drive controller protection features.
• 
InH
 should not be enabled for typical applications of this equipment.
• 
InH
 should be enabled only in extraordinary situations where a thorough risk analysis demonstrates that the 
presence of adjustable speed drive protection poses a greater risk than personnel injury or equipment damage.
Failure to follow these instructions will result in death or serious injury.
  To change the assignment of this parameter press the “ENT” key for 2 s.
T
Parameter that can be modified during operation or when stopped.
I-O-
drC-
CtL-
FUN-
FLt-
COM-
2 s