Vermont Casting 36CDVTRN 사용자 설명서

다운로드
페이지 40
9
CDV Series Direct Vent Gas Fireplace
20010175
The electrical junction box has been fitted standard on 
this model to allow for the easy connection of an op-
tional fan kit. 
To connect the electric box to the house electrical sup-
ply follow the steps below.
1.  Unscrew the retaining screw holding the electric 
cover to the outside of the unit. (Fig. 7)
2.  Remove the knockout from the electric cover plate.
3.  Insert the wire connector through the hole in the 
electric cover plate and secure.
4.  Insert the house wire through the connector on the 
cover plate.
5.  Secure the wires from the receptacle to the incoming 
line.
6.  The receptacle has four wires connected to it. The 
receptacle is set up for a split system. The top plug 
of the receptacle is wired separately from the bottom 
one.
7.  Green is ground. White is neutral, Black and red are 
line voltage to each plug on the receptacle.
Ensure that the power to the supply line 
has been disconnected before commenc-
ing this procedure.                
FP1597
Fig. 7  Electric receptacle.
FP1597
receptacle install
12/05
OUTSIDE
INSIDE
BACK OF UNIT
Electric Receptacle
Electric Receptacle 
Cover Plate
Your fireplace is approved to be vented either through 
the side wall, or vertically through the roof.
• 
Only CFM Corporation venting components specifi-
cally approved and labelled for this fireplace may be 
used.
• 
Vent terminations shall not be recessed into a wall or 
siding.
• 
Horizontal venting which incorporates the twist lock 
pipe must be installed on a level plane without an 
inclining or declining slope.
• 
Horizontal venting which incorporates the use of flex 
venting shall have an inclining slope from the unit of 
1” (25 mm) per 24” (610 mm).
General Venting
There must not be any obstruction such as bushes, 
garden sheds, fences, decks or utility buildings within 
24” (610mm) from the front of the termination hood.
Do not locate termination hood where excessive snow 
or ice build up may occur. Be sure to check vent termi-
nation area after snow falls, and clear to prevent ac-
cidental blockage of venting system. When using snow 
blowers, make sure snow is not directed towards vent 
termination area.
Location of Vent Termination 
It is imperative the vent termination be located observ-
ing the minimum clearances as shown on the next  
page.
*Check with local codes or in absence of same with 
CSAB149.1 Installation Codes (1991) for Canada or fol-
low the current National Fuel Gas Code, ANSI Z223.1/
NFPA 54 for installations in the USA.