Toshiba 4200FA 전단
TOSHIBA
4200FA XT UPS
Installation Planning Guide for 15-80kVA UPS
Standard System: 208v Input, 208/120V Output
Rev. 1.03
Page 1 of 2
4200FA-IPG-208v-XT1
General Mechanical Information
Dimensions
(W x D x H)
Approximate Full-Load Heat Loss
UPS kVA/ kW Rating
Inches
Weight
Lbs.
kBTU’s / Hr
15 kVA/12 kW
20 x 36.25 x 59.85
900
5.7
25 kVA/ 20 kW
20 x 36.25 x 59.85
910
7.6
30 kVA/ 24 kW
20 x 36.25 x 59.85
915
9.1
50 kVA/ 40 kW
35.59 x 38.19 x 59.39
2,548
17.7
80 kVA / 64 kW
44 x 31 x 74
2,200
40.0
Primary AC Input (208V 3-Phase / 3-Wire)
Maximum Input Power
Demand
Suggested External
Overcurrent Protection
Suggested Minimum Feeder
Wire Size Per Phase
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
kVA
PF
Amps
Amps
AWG or kcmil at 75º C Temp. Rating
Feet
15
>0.97
45.7
60 AT
(1) x 8
380
25
>0.97
76.3
90 AT
(1) x 4
380
30
>0.97
92.4
125 AT
(1) x 3
380
50
>0.97
152.6
200 AT
(1) x 1/0
380
80
>0.98
244.3
300 AT
(1) x 300
380
Optional Alternate AC Input (208/120V 3-Phase / 4-Wire)
Maximum Input Power
Demand
Suggested External
Overcurrent Protection
Suggested Minimum Feeder
Wire Size Per Phase / Neutral
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
kVA
Amps
Amps
AWG at 75º C Temp. Rating
Feet
15
41.6
60 AT
(1) x 8 / (1) x 6
380
25
69.4
90 AT
(1) x 4 / (1) x 2
380
30
83.3
110 AT
(1) x 3 / (1) x 1
380
50
138.8
175 AT
(1) x 1/0 / (1) x 4/0
380
80
222.1
300 AT
(1) x 4/0 / (1) x 400
380
Battery Input (288VDC Nominal)
Battery Capacity Required
for Full Load Output
Maximum Discharge
at Full Load Output
Suggested External
Overcurrent Protection
Suggested Minimum Feeder
Wire Size Per Phase
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
kVA
kWB
Amps DC
Amps
AWG or kcmil at 75º C Temp. Rating
Feet
15
13.33
61.7
90 AT
(1) x 6
70
25
22.22
102.8
125 AT
(1) x 2
70
30
26.67
123.0
175 AT
(1) x 1
70
50
44.44
205.7
225 AT
(1) x 4/0
70
80
71.11
329.2
400 AT
(2) x 3/0
70
AC Output (208/120V 3-Phase / 4-Wire)
Rated Output Power
Suggested External
Overcurrent Protection
Suggested Minimum Feeder
Wire Size Per Phase / Neutral
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
kVA
PF
Amps
Amps
AWG or kcmil at 75º C Temp. Rating
Feet
15
0.8
41.6
60 AT
(1) x 8 / (1) x 6
380
25
0.8
69.4
90 AT
(1) x 4 / (1) x 2
380
30
0.8
83.3
110 AT
(1) x 3 / (1) x 1
380
50
0.8
138.8
175 AT
(1) x 1/0 / (1) x 4/0
380
80
0.8
222.1
300 AT
(1) x 4/0 / (1) x 400
380