Sidewall direct
 
venting
Vent/air termination – sidewall
TO BOILER
INTAKE AIR
CONNECTION
FROM BOILER
VENT PIPE
CONNECTION
TERMINATION
PLATE
BIRD SCREEN
GRADE OR
SNOW LINE
12”
MIN
BIRD SCREEN
12” MIN
15” MAX
Do not exceed the maximum lengths of the 
outside vent piping shown in FIG. 4-1B.  
Excessive length exposed to the outside 
could cause freezing of condensate in the 
vent pipe, resulting in potential boiler 
shutdown.
Figure 4-1B Alternate PVC/CPVC/ Polypropylene Sidewall 
Termination of Air and Vent w/Field Supplied Fittings
 WARNING
If using the alternate sidewall termination:
3.  The air piping must terminate in a down-turned elbow 
as shown in FIG. 4-1B.  This arrangement avoids 
recirculation  of flue products into the combustion air 
stream.
4.  The vent piping must terminate in an elbow pointed 
outward or away from the air inlet, as shown in FIG. 4-1B.
TO BOILER
INTAKE AIR
CONNECTION
FROM BOILER
VENT PIPE
CONNECTION
VENT / AIR
TERMINATION
GRADE OR
SNOW LINE
12"
MIN
12"
MIN
TO
OVER-
HANG
POSSIBLE ORIENTATIONS
Model
Kit Number
Vent Size
55 - 110
KIT30044
2 inch vent
110 - 285
KIT30045
3 inch vent
399 
KIT30046
4 inch vent
Table 4A Sidewall Vent Kit
             
Installation & Operation Manual
22
Follow instructions below when 
determining vent location to avoid 
possibility of severe personal injury, 
death, or substantial property damage.
A gas vent extending through an exterior 
wall shall not terminate adjacent to a wall 
or below building extensions such as eaves, 
parapets, balconies, or decks.  Failure to 
comply could result in severe personal 
injury, death, or substantial property 
damage.
Determine location
Locate the vent/air terminations using the following guidelines:
1.  The total length of piping for vent or air must not exceed 
the limits given in the General Venting Section on page 16 
of this manual.
2.  You must consider the surroundings when terminating 
 
the   vent and air:
a.  Position the vent termination where vapors will 
  not damage nearby shrubs, plants or air 
 
conditioning equipment or be objectionable.
b.  The flue products will form a noticeable plume as 
 
they condense in cold air.  Avoid areas where the 
 
plume could obstruct window views.
c. Prevailing winds could cause freezing of 
 
condensate and water/ice buildup where flue 
 
products impinge on building surfaces or plants.
d.  Avoid possibility of accidental contact of flue 
 
products with people or pets.
e.  Do not locate the terminations where wind eddies 
 
could affect performance or cause recirculation, 
 
such as inside building corners, near adjacent 
 
buildings or surfaces, window wells, stairwells, 
 
alcoves, courtyards, or other recessed areas.
 WARNING
 WARNING
 WARNING Sidewall vent and air inlet terminations 
must terminate in the same pressure zone.
f.  Do not terminate above any door or window. 
 
 
Condensate can freeze, causing ice formations.
g.  Locate or guard vent to prevent condensate damage 
 
to exterior finishes.
Figure 4-1A PVC/CPVC/Polypropylene  Sidewall 
Termination of Air and Vent