Installation & Operation Manual
34
6  
Hydronic piping  
Near boiler piping components
1.  Boiler system piping:
 
Boiler system piping MUST be sized per the pipe 
 
requirements listed in Table 6A.  Reducing the pipe size 
 
can restrict the flow rate through the boiler, causing 
 
inadvertent high limit shutdowns and poor system 
 
performance.  Flow rates are based on 20 feet of piping,   
 
4 - 90° elbows, and 2 - fully ported ball valves. 
2.  Boiler circulating pump:
 
A Grundfos UPS15-58FC pump for Models 55 - 155 
 
and a Grundfos  UPS26-99FC  pump for Models 199 - 
 
399 will be provided by the factory as the boiler circulation 
 
pump based on 20 feet of piping, 4 - 90° elbows, and 2 - fully 
 
ported ball valves.
 
Knight wall mount boilers are capable of controlling a 
 
variable speed boiler circulator.  Variable speed 
 
circulators MUST be sized to meet the specified 
 
minimum flow requirements listed in FIG. 6-2 on page 36 
 
at full speed.
3.  Domestic hot water circulating pump:
 
Field supplied.  The pump MUST be sized to meet 
 
the specified minimum flow requirements listed in 
 
 
 
FIG. 6-2.  Consult the indirect water heater operating 
 
guide to determine flow characteristics for the selected 
 product 
used.
4. Boiler 
isolation 
valves:
 
Field supplied.  Full port ball valves are required.  Failure 
 
to use full port ball valves could result in a restricted flow 
 
rate through the boiler.
5. Check 
valves:
 
Field supplied.  Check valves are recommended for 
 
installation as shown in FIG.’s 6-3 through 6-10.  Failure 
 
to install check valves could result in a reverse flow 
 
condition during pump(s) off cycle.
6.  Domestic indirect hot water isolation valves:
  Field supplied.  Full port ball valves are 
 
required.  Failure to use full port ball valves could 
 
result in a restricted flow rate through the boiler.
7.  Anti-scald mixing valve:
 
Field supplied.  An anti-scald mixing valve is 
 
recommended when storing domestic hot water above 
 115°F.
8. Unions:
 
Field supplied.  Recommended for unit serviceability.
9.  Temperature and pressure gauge:
 
Factory supplied.  The temperature and pressure gauge is 
 
shipped loose.  It is the responsibility of the contractor to 
 
install the temperature and pressure gauge on the boiler 
 water 
outlet.
10. Pressure relief valve:
 
Factory supplied.  The pressure relief valve is sized to 
 ASME 
specifications.
11. Boiler purge valve:
 
Factory supplied.  The boiler purge valve is used to 
 
remove entrapped air from the heat exchanger during 
 start-up.
12.  System temperature sensor:
  Lochinvar supplies a system temperature sensor. 
 
 
The sensor is to be installed in the heating loop 
 
downstream from the boiler hot water piping and 
 
heating loop junction.  Typically the sensor will be 
 
located far enough downstream to sense system diluted 
 water 
temperature. 
13. Indirect water heaters:
 
The Knight wall mount boiler may be piped to an indirect 
 
water heater to heat domestic hot water with the space heat 
 
transfer medium.  As depicted in the piping diagrams on 
 
page 38 thru 47, there are two options when utilizing an 
 
indirect water heater.
 
A.  The space heating piping will branch off to flow the 
 
 
space heat transfer medium through a single wall 
 
 
heat exchanger coil inside the indirect water heater.
 
 
 
B.  The indirect water heater is connected to the system 
 
 
supply piping.  A pump controlled by the Knight 
 
 
(wall mount) boiler’s control will regulate the flow of 
 
 
water through the indirect water heater.  The indirect 
 
 
water heater’s temperature will be regulated by the 
 
 
Knight (wall mount) boiler’s control.
 
The Knight wall mount boiler is pre-configured to control 
 
the operation of the DHW pump with Domestic Hot Water 
 
Prioritization programming.  The DHW programming is 
 
designed to control and balance the space heating 
 
demand by switching between DHW and space heating.
 
Lochinvar offers the Squire which is a series of indirect 
 
water heaters. The Squire features a stainless steel vessel 
 
with a single wall stainless steel heat exchanger.
 WARNING The National Standard Plumbing Code, the 
National Plumbing Code of Canada and the 
Uniform Plumbing Code limit the pressure 
of the heat transfer fluid to less than the 
minimum working pressure of the potable 
water system up to 30 psi maximum.  Also, 
the heat transfer fluid must be water or 
other non-toxic fluid having a toxicity of 
Class 1, as listed in Clinical Toxicology of 
Commercial Products, 5
th
 Edition.
14. Y-Strainer:
 
Field supplied.  A Y-strainer or equivalent multipurpose 
 
strainer is recommended at the inlet of the heat exchanger 
 
to remove system particles from older hydronic systems and 
 
protect newer systems.