Honeywell MS-9600UDLSE 사용자 설명서

다운로드
페이지 208
MS-9600LS Series Manual — P/N 52646:B2  2/12/2010
31
Accessories
Product Description
4. Select the address and configuration options for the ANN-S/PG module as described in the 
Programming section of this manual (refer to “ANN-BUS Options” on page 121).
Note that the Auto-configure feature allows the programmer to quickly bring all installed 
ANN-BUS modules online (refer to “Auto-Configure” on page 131).
5. Connect a printer to the ANN-S/PG Parallel or Serial connectors (refer to Figure 1.7).  Only 
one printer can be connected.
Specifications
Operating Voltage: 24 VDC
Current (Alarm and Standby): 45 mA
Ambient Temperature: 32
o
F to 120
o
F (0
o
C to 49
o
C)
Max. Wiring Distance from FACP: 6,000 ft. (1,800 m)
Mounting: Surface
Dimensions: 6”W x 7-3/4”H x 1-7/16”D (15.2 cm W x 19.7 cm H x 3.7 cm D)
For indoor use in a dry location only
PRN 6F Printer Installation
When connected to the FACP via the ANN-S/PG module, the PRN-6F prints the status changes 
within the control panel and time-stamps the printout with the time of day and date that the event 
occurred.  It provides 80 columns of data on standard 9” x 11” tractor-feed paper.  This section con-
tains information on connecting a printer to the control panel and setting the printer options.
Connecting PRN-6F Printer
Remote printers require a primary AC power source.  If required for the fire alarm system configu-
ration (for example, a Proprietary Fire Alarm System), a remote printer requires a secondary power 
source (battery backup).  Since a secondary power source is not provided as a standard feature, a 
separate UL-listed Uninterruptible Power Supply (UPS) should be used.  The building emergency 
power supply may be used, as long as it meets the power continuity requirements of NFPA 72.  
Refer to NFPA 72 for further details.
Connect the remote printer to the FACP via the ANN-S/PG module using a standard DB-25 cable.  
One end of the cable will plug into the DB-25 connector on the PRN printer and the other end plugs 
into the parallel connector on the ANN-S/PG module.  Note that the 9-pin DB-9 port on the ANN-
S/PG is used to connect a serial printer.  The 25-pin port is used for a Centronics parallel printer 
cable.  Connect either a serial or parallel printer, but not both at the same time.
Setting Printer Options
Refer to the documentation supplied with the PRN-6F printer for instructions on using the printer 
menu controls.  Set the printer options (under the menu area) as shown in the following table: 
Option
Setting
Option
Setting
Font
HS Draft
CPI
10CPI
LPI
6 LPI
Skip
0.5
ESC Character
ESC
Emulate
Epson FX-850
Bidirectional Copy
ON
I/O
CG-TAB
Graphic
    Buffer
40K
Country
E-US ASCII
Serial
Auto CR
OFF
    Baud
9600 or 2400
Color Option
Not Installed
    Format
7 Bit, Even, 1 Stop
Formien
    Protocol
XON/XOFF
    Lines
6LPI=60
Character Set
Standard
Table 1.2  PRN-6F Setup Options