3-2. Outdoor Unit
RAV-SP1104AT-E, SP1104ATZ-E, SP1104ATZG-E, RAV-SP1404AT-E, SP1404ATZ-E, SP1404ATZG-E
*
This compressor has 4-pole motor. The value when compressor frequency (Hz) is measured by a clamp
meter becomes 2 times of No. of compressor revolutions (rps).
meter becomes 2 times of No. of compressor revolutions (rps).
RAV-SP1404AT-E, RAV-SP1404ATZ-E, RAV-SP1404ATZG-E
*
This compressor has 4-pole motor. The value when compressor frequency (Hz) is measured by a clamp
meter becomes two times of No. of compressor revolutions (rps).
meter becomes two times of No. of compressor revolutions (rps).
3-3. Systematic Diagram of Refrigerating Cycle
RAV-SP1104AT-E, RAV-SP1104ATZ-E, RAV-SP1104ATZG-E
Standard
Cooling
Overload
Low load
Standard
Heating
Overload
Low load
Pressure
(MPa)
(kg/cm²g)
Pd
Ps
Pd
Ps
2.72
0.90
27.8
9.2
3.34
1.07
34.1
10.9
1.75
0.76
17.9
7.8
2.59
0.69
26.4
7.0
3.13
1.05
31.9
10.7
2.40
0.21
24.5
2.1
Pipe surface temperature (°C)
Discharge
Suction
Indoor heat
Outdoor heat
exchanger
exchanger
(TD)
(TS)
(TC)
(TL)
(TE)
73
12
10
46
38
80
9
13
51
45
47
8
6
33
25
75
3
43
2
2
72
16
53
12
13
97
–22
42
–19
–18
Compressor
drive revolution
frequency
(rps)
51
55
21
53
26
90
Indoor
fan
HIGH
HIGH
LOW
HIGH
LOW
HIGH
Indoor/Outdoor
temp. conditions
(DB/WB) (°C)
Indoor
Outdoor
27/19
35/–
32/24
43/–
18/15.5
–5/–
20/–
7/6
30/–
24/18
15/–
–15/–
Standard
Cooling
Overload
Low load
Standard
Heating
Overload
Low load
Pressure
(MPa)
(kg/cm²g)
Pd
Ps
Pd
Ps
2.57
0.99
26.2
10.1
3.30
1.09
33.7
11.1
1.74
0.75
17.8
7.7
2.32
0.73
23.7
7.4
3.22
1.17
32.9
11.9
2.17
0.30
22.1
3.1
Pipe surface temperature (°C)
Discharge
Suction
Indoor heat
Outdoor heat
exchanger
exchanger
(TD)
(TS)
(TC)
(TL)
(TE)
66
14
12
44
38
78
9
13
49
43
46
7
5
32
25
65
3
39
2
3
73
19
54
14
15
87
–15
38
–14
–13
Compressor
drive revolution
frequency
(rps)
38
53
21
43
26
71
Indoor
fan
HIGH
HIGH
LOW
HIGH
LOW
HIGH
Indoor/Outdoor
temp. conditions
(DB/WB) (°C)
Indoor
Outdoor
27/19
35/–
32/24
43/–
18/15.5
–5/–
20/–
7/6
30/–
24/18
15/–
–15/–
In cooling operation
In heating operation
In heating operation
Ø25 × L180
Ø25 × L210
TS sensor
TO sensor
TE sensor
TD sensor
TL sensor
Cooling: High pressure
Heating: Low pressure
Heating: Low pressure
Cooling: Low pressure
Heating: High pressure
Heating: High pressure
Check joint
Heat exchanger
Ø8, 2 rows, 52 stages
FP1.45, flat fin
Accumulator
(2500cc)
Rotary compressor
(DA422A3F-25M)
PMV
Capillary
Ø4 ×Ø3 (6 pcs.)
Ø4 ×Ø3 (6 pcs.)
Strainer
Strainer
Refrigerant pipe
at liquid side Ø9.5
Packed valve
at liquid side Ø9.5
Packed valve
Refrigerant pipe
at gas side Ø15.9
Ball valve
at gas side Ø15.9
Ball valve
Distributor
Muffler