 D  How to check miswiring and serial signal error
• Unit cannot operate neither by the remote controller nor by EMERGENCY OPERATION switch.
  Indoor unit does not operate.
• OPERATION INDICATOR lamp flashes ON and OFF every 0.5-second.
  Outdoor unit does not operate.
Turn OFF the power supply.
Is there rated voltage AC in 
the power supply?
Yes
No
Turn ON the power supply.
Check the power supply.
Is there rated voltage between 
outdoor terminal block S1 and 
S2?
No
Check the wiring.
Press EMERGENCY OPERATION switch once.
Does the left lamp of OPERATION INDICATOR 
lamp light up? <Confi rmation of the power to 
the indoor unit>
Yes
No
Is serial signal error indicated 6 minutes later?
Yes
No
Is there any miswiring, poor 
contact, or wire disconnec-
tion of the indoor/outdoor 
connecting wire?
Is fuse (F65) broken?
Yes
Correct them.
No
A
Turn OFF the power supply.
Check once more if the indoor/outdoor 
connecting wire is not miswiring.
Short-circuit outdoor terminal block S2 
and S3.  1
B
1. Miswiring may damage indoor electronic control 
P.C. board during the operation.
 
Be sure to confi rm the wiring is correct before 
the operation starts.
Turn ON the power supply.
Does the LED on the inverter P.C. board or 
the outdoor electronic control P.C. board 
repeat "3.6-second-OFF and 0.8-second-
ON quick blinking"?    
Yes
No
(Lighted 
or not 
lighted)
Replace the inverter P.C. board or the 
outdoor electronic control P.C. board.
2
2. Be careful to the residual       
voltage of smoothing capacitor.
Turn OFF the power supply.
Remove the short-circuit between out-
door terminal block S2 and S3.
Turn ON the power supply.
Is there amplitude of 10 to 20 VDC 
between outdoor terminal block S2 and 
S3?  <Confi rmation of serial signal>
Yes
No
Is there any error of the in-
door/outdoor connecting wire, 
such as the damage of the wire, 
intermediate connection, poor 
contact to the terminal block?
Yes
Replace the indoor/out-
door connecting wire.
Is there rated voltage between 
indoor terminal block S1 and S2?
<Confi rmation of power voltage>
No
No
Is there any error of the in-
door/outdoor connecting wire, 
such as the damage of the wire, 
intermediate connection, poor 
contact to the terminal block?
Yes
Replace the indoor/out-
door connecting wire.
No
Replace the indoor electronic control P.C. board.
Yes
Be sure to release the failure-mode recall function 
after checking.
Yes
Turn OFF inverter-controlled lighting 
equipment.
Turn OFF the power supply and then 
turn ON again.
Press EMERGENCY OPERATION 
switch.
A
Is serial signal 
error indicated 6 
minutes later?
B
Yes
Reinstall 
either the unit 
or the light 
each other 
away.
Attach a fi lter 
on remote 
control receiv-
ing section 
of the indoor 
unit.
No