Clearances to any combustibles when measured directly from the  floor protector to the ceiling must be a 
minimum of 84" (2134 mm).  Clearances to any combustibles when measured directly from the  front of the 
stove  must be a minimum of 48" (1219 mm).  The stove must also be placed so as to maintain the minimum 
clearances to combustible walls  specified for each type of connector  used.  See Table 1.3 below for all  
clearance measures.  Refer to Figure 1.3 for a diagram of each of the measures A through C. 
 
 
 
Single walled connector 
Listed double walled 
connector 
Unit: 
 
 
To sidewall   (A) 
18" (406 mm) 
18" (406 mm) 
To back wall    (B) 
18" (406 mm) 
18" (406 mm) 
To corner 
(C) 
12" (305 mm) 
12" (305 mm) 
 
 
 
 
TABLE 1.3 Clearances to combustible materials  
 
 
 
 
 
FIGURE 1.3 Clearances to combustible materials