8-6.  Automatic Operation
(1)  Normal
Set temperature can be shifted  ± 4°F (2°C), in 2°F (1°C) steps.
If operation commences again within 2 hours of the previous operation, the previous setting is applied.
(2)  Changing fan speed “Automatic”
Fan speed is automatically selected by the temperature difference between the room temperature (T
R
) and set
temperature (T
S
).
During Heating Operation
During Cooling Operation
Room temperature at start of operation
Temperature set automatically
Operation mode
T
R
°F (°C)
°F (°C)
88 (30) 
T
R
82 (27)
84 (24) 
T
< 88 (30)
80 (26)
Cooling
80 (26) 
T
< 84 (28)
78 (25)
72 (22) 
T
< 80 (26)
76 (24)
Dry
T
< 72 (22)
76 (24)
Heating
Room temperature (T
R
) and set temperature (T
S
)
Fan speed
T
R
T
S
+ 4°F (2°C)
H / High
T
S
+ 4°F (2°C) > T
R
T
S
+ 2°F (1°C)
M / Medium
T
S
+ 2°F (1°C) 
T
R
T
S
L / Low
T
S
> T
R
(Thermo. OFF)
L / Low
Room temperature (T
R
) and set temperature (T
S
)
Fan speed
T
R
T
S
H / High
T
S
< T
R
< T
S
+ 2°F (1°C)
M / Medium
T
S
+ 2°F (1°C) 
T
R
(Thermo. OFF)
LL / Very Low