Product Description
Product Features
Primary applications for the audio panels include structures such as restaurants, schools, auditori-
ums, places of worship, buildings with occupancies over 50, etc.  The ACC-25/50 Series is 
designed to interface directly to addressable or conventional fire alarm control panels or can be 
used with the Audio Command Center Distributed Audio (ACC-25/50DA) panel to distribute audio 
in systems that require more than 50 watts.
1.1  Product Features
25 watts of 25 V
RMS
 audio power (expandable to 50 watts) per panel
Optional 70.7 V
RMS
 conversion module available for each amplifier (note that speaker wiring 
continues to be supervised in standby, alarm and when background music is playing with this 
option module installed)
Modular design for maximum system flexibility
Unobstructed module access and removable terminal blocks for ease of servicing and module 
replacement
Designed to allow easy system expansion
Five Command Input Circuits:
CMD1 and CMD2 are field selectable to be activated from 12 or 24 VDC Notification 
Appliance Circuits (reverse polarity) or contact closures
CMD3, CMD4, and CMD5 are activated by contact closures
Speaker Circuits
single Style Y or Z speaker circuit (one ACC-AAM25 Audio Amplifier provided with base 
unit)
two Style Y or Style Z speaker circuits (with optional second ACC-AAM25 Audio 
Amplifier installed)
eight Style Y or four Style Z speaker circuits (only on ACC-25/50ZS or ACC-25/50ZST 
Panel with ACC-ZSM Zone Splitter Module)
ACC-25/50ZS and ACC-25/50ZST can be controlled by an FACP via the ACS (EIA-485) link 
to the ACC-ZPMK.  ACS compatible FACPs include the MS-9600, MS-9200(E), MS-
9200UD, MS-9200UDLS and MS-5210UD.
Integral supervised microphone
Microphone time-out feature which reverts back to prerecorded message if emergency page 
exceeds three minutes
Standard, prerecorded message: 
 “May I have your attention please.  May I have your attention please.  The signal you 
have just heard indicates a report of a fire in this building.  Please proceed to the nearest 
exit and leave the building.  Do not re-enter the building unless directed to do so by the 
proper authorities.”
Field-selectable message and custom message field recording capability using local 
microphone or two compatible audio input jacks
Two External Audio Inputs for recording custom message from compatible source or playing 
music over the system with prior approval of the local Authority Having Jurisdiction (AHJ)
Multiple duration message capability: one 60 second, two 30 second, three 20 second, four 15 
second or five 12 second custom messages
Integral tone generators field selectable for steady, slow-whoop, high-low or chime tones
Higher wattage capability available by using the Audio Command Center Distributed Audio 
(ACC-25/50DA) panel
Powered by integral AC power supply or batteries during AC fail
Programmable delay of immediate, 2 hours or 6 hours reporting of AC Loss
Piezo sounder for local trouble