Audio Command Center Series Manual — P/N 51889:E1 6/8/2010
Field Programming
ACC-ZPMK Zone Page Module (ACC-25/50ZS & ACC-25/50ZST)
2.8.1 S1 DIP Switch Settings on ACC-ZPMK
•
Switches 1, 2 and 3 are used to configure the ACC-25/50ZS/T for operation with a specific
FACP as shown in the following table:
FACP as shown in the following table:
•
Switch 4 - not used (future)
•
Switch 5 - not used (must be set to OFF)
•
Switches 6, 7 and 8 - used to set the number of ACC-25/50DAZS Distributed Audio Panels
connected to the ACC-25/50ZS or 25/50ZST as shown in the following table:
connected to the ACC-25/50ZS or 25/50ZST as shown in the following table:
SWITCH
1
SWITCH
2
SWITCH
3
CONFIGURED FOR OPERATION WITH FOLLOWING FIRE ALARM
CONTROL PANEL
OFF
OFF
OFF
MS-9200UD version 1 or non-ACS/ANN-BUS FACP connected
(factory default setting)
OFF
OFF
ON
ACS Protocol: MS-5210UD
OFF
ON
OFF
ACS Protocol: MS-9200
OFF
ON
ON
ACS Protocol: MS-9600 version 1
ON
OFF
OFF
ACS Protocol: MS-9600 version 2
ON
OFF
ON
ACS Protocol: MS-9200UDLS or MS-9200UD version 2 or 3
ON
ON
OFF
ANN-BUS Protocol:
MS-9600LS Version 4 or higher
MS-9200UDLS Version 4 or higher
MS-5UD-3, MS-5UD-7, MS-10UD-3 & MS-10UD-7 Version 2 or higher
ON
ON
ON
future use
Table 2.8 FACP Configuration
SWITCH
6
SWITCH
7
SWITCH
8
NUMBER OF ACC-25/50DAZS DISTRIBUTED AUDIO PANELS
CONNECTED TO ACC-25/50ZS or 25/50ZST
OFF
OFF
OFF
No ACC-25/50DAZS panel connected
OFF
OFF
ON
1 ACC-25/50DAZS panel connected
OFF
ON
OFF
2 ACC-25/50DAZS panels connected
OFF
ON
ON
3 ACC-25/50DAZS panels connected
ON
OFF
OFF
4 ACC-25/50DAZS panels connected
ON
OFF
ON
5 ACC-25/50DAZS panels connected
ON
ON
OFF
invalid
ON
ON
ON
invalid
Table 2.9 Quantity of ACC-25/50DAZS Panels Connected