Siemens siemens compact universal controllers 데이터 시트

다운로드
페이지 10
4/10 
Building Technologies 
 
CC1N7865en 
HVAC Products 
 
01.09.2005 
Technical data 
Mains voltage 
AC 110...240 V +10 % / -10 % 
Mains frequency 
48...63 Hz 
Safety class 
II to DIN 0631 
Mounting position 
optional 
Terminals for  
2 x 1.5 mm² or 1 x 2.5 mm² 
Power consumption 
max. 10 VA 
Safety extra low-voltage 
DC 24 V 
Contact rating of the control outputs 
(relays «K1...K3») 
Up to 2 x 10
5
 switching cycles 
Up to 10
7
 switching cycles 
 
 
2 A / AC 24...240 V 
0.1 A / AC 24...240 V 
Weight complete with housing 
approx. 760 g 
Recommended actuator running time 
15...60 s 
Degree of protection of housing 
- Front 
- Base 
 
IP 65, EN 60529 
IP 20, EN 60529 
 
Storage 
DIN EN 60 721-3-1 
Temperature range 
-20...+60 °C 
Humidity 
< 75 % r.h. 
Transport 
 
Temperature range 
-40...+70 °C 
Humidity 
< 75 % r.h. 
Operation 
 
Temperature range 
-20...+50 °C 
Humidity 
< 75 % r.h. 
 
Condensation, formation of ice and ingress of water are not permitted! 
General controller data 
Environmental 
conditions