Local Test Mode
Local Test Mode provides the ability to control a 1641
Receiver without a code line connected.  This capability can be
used with any model 1641 Receiver.
The Local Test Mode feature is operated as follows, using the
internal rotary switches S9 and S11, and internal button switch
S8.  See Figures 4, 5, or 6 on the following pages for the
location of these switches on the main PCB (either 1641M,or
S models).
1. Place switch position 3 of DIP switch S7 to the ON, Local
Test Mode, position.
2. Select the desired function from the Local Test Mode Setup
list, shown in Table 3.
3. Dial the corresponding switch settings on rotary switches
S9 and S11.
4. Press S8 on the PCB to activate selected setting.
Note: Reset all Rotary and DIP switches properly after testing
is complete.
Table 3 - Local Test Mode Setup
Function 
S9
S11
Pan Left
0
1
Pan Right
0
2
Tilt Up
0
3
Tilt Down
0
4
Focus Near
0
5
Focus Far
0
6
Zoom Tele
0
7
Zoom Wide
0
8
Iris Open
0
9
Iris Close
1
0
SET Shot
1
1
CALL Shot
1
2
Aux 1 On
1
3
Aux 1 Off
1
4
Aux 2 On
1
5
Aux 2 Off
1
6
Autopan using Auxiliary 1
The Pan/Tilt unit internal autopan control is obtained by
changing the auxiliary 1 relay from an unpowered relay to a
powered relay with 24 VAC on it.  To configure the Receiver
for autopan using auxiliary 1, move jumper J22 (see Figure 4,
5, or 6) to the autopan position.
Note: The total of all 24 volt Pan/Tilt motor currents and
auxiliaries is not to exceed 2.0 amps (“-2” models) for
continuous operation. (see notes to Table 1, page 2).
RS-232 Receiver (1641S) Setup
For RS-232 code models (1641S), the S1 and S2 DIP switches
on the RS-232 Receiver Module must be set to the following
positions.  See Figure 5 on page 7 for location of these DIP
switches on the 1641S Receiver Module PCB.
DIP Sw.
1
2
3
4
5
6
7
8
S1
On
On
Off
Off
Off
Off Off Off
S2
---
Reserved for Future Use
---
For RS-232 code, switch position 3 of DIP switch S7 must be
in the OFF position and rotary switches S11 and S9 must be set
as shown in Tables 4 and 5 below.  Switch S11 specifies the
type of code and switch S9 is for RS-232 baud rate.  The
factory default settings are shown in bold type.  See Figure 5
on page 7 for location of these switches on the main PCB.
Table 4 -  Code Type - Rotary Switch S11
Position
Function 
0
2-byte RS-232 codes - for 1983 Code Converter
and similar coded units
1
3-byte RS-232 codes - for 2091 Code Generator,
1983CS536, and similar coded units
2
ASCII codes (Repeating) - for System Keyboards
and similar units
ASCII codes (Make/Break type)- for Special
Keyboards and similar units
4-7,9
not used (position 8 is for Coax, see below)
Table 5 -  RS-232 Baud Rate - Rotary Switch S9
Position
Function
0
9600
1
4800
2
2400
3
1200
4-9
not used
SETUP
5