MINUTEMAN
®
 CPE
 Series Specifications
© Copyright 2006, Para Systems, Inc.  Product specifications are subject to change without notice. MINUTEMAN is a registered trademark and MINUTEMAN CPE is a trademark of Para Systems, 
Inc.  
MINUTEMAN UPS / Para Systems, Inc.
1455 LeMay Drive, Carrollton, TX 75007
Phone 800.238.7272  +1 972.446.7363  Fax +1 972.446.9011
PN-34000289 - 10-09
Model
 
 
 
 
    
    1000 VA 
                              2000 VA 
              3000 VA
Input 
 
Voltage (VAC)  
80 - 140
Frequency
50/60 +/- 5% (Auto Sensing)
Phase
Single
 
Input Power Factor Correction  
>0.98 (Full Load)
Input Power Cord (NEMA)
5-15P
5-20P
  L5-30P
Output
Voltage (VAC)  
100/110/115/120
Capacity (VA/W)  
1000VA/700W
2000VA/1400W
3000VA/2100W
Rated Power Factor
0.7 Lagging
Load Power Factor Range
0.5 Lagging to Unity within KW Rating of Unit
Wave Form
Sine Wave, THD <3% (no load to full load)
Voltage Regulation
+/- 2%
Transient Response (ms)
+/- 4% Under Full Load, Change and Corrected within 60 ms
Frequency Stability
+/- 0.5 Hz (Free Running)
Synchronization  
Slew Rate: 1 Hz/Sec. Max Synchronizing Window +/-5%
Transfer Time  
0 ms
Crest Factor
3:1
Runtime (Full Load)
>8 min.
>7 min.
>8 min.
DC Start
Yes
Outlets (NEMA) 120 VAC
4 x 5 - 15R  
4 x 5 - 15R + 2 x 5 - 15/20R
6 x 5 - 15R + 2 x 5 - 15/20R
Display
LED Indicators  
Utility, Battery Low, Inverter, Bypass, Test OK, Overload Fault, Load/Battery Level, and System Fault Conditions
Self Diagnostics  
On-Demand Push Button
Alarms
Audible and Visual
Line Failure, Battery Low, Transfer to Bypass, Overload, System Fault Conditions
Physical
Tower Net Dimensions (WxHxD, in.)
5.8 x 8.78 x 15.8
5.1 x 14.4 x 18.9
7.5 x 14.4 x 17.8
Tower Net Weight (lbs. / kg)
33 / 15  
60 / 27
79 / 36
Environmental
Operating Temperature  
0
°
C - 40
°
C
Altitude
0 to +10,000 ft
Humidity
30 to 90% RH Maximum, Non-condensing
Noise
< 45 dB at 1 meter
Safety Conformance  
Safety Standard  
EN500091-1, UL1778, CSA 22.2
EMC Standard  
EN500091-2, EN61000-3-2, EN61000-3-3, FCC Class A
Agency Marks  
UL, CE, cUL
Tower Models (Rear View)