Gas Conversion:
No attempt shall be made to convert the Power™ burner from 
the gas specified on the model/serial rating plate for use with a 
different gas type without consulting the serving gas supplier. The 
conversion kits supplied with the Power™ burner must be used. 
See “Gas Conversions” section for instructions.
Gas Pressure Regulator
The gas pressure regulator supplied with this Power™ burner 
must be used. The inlet (supply) pressure to the regulator should 
be as follows for proper operation:
LP Gas:
Set pressure: 11" (28 cm) WCP
Inlet (supply) pressure: 11" to 14" (28 cm to 35.5 cm) WCP
Natural Gas:
Set pressure: 4" (10.2 cm) WCP
Inlet (supply) pressure: 7" to 14" (17.8 cm to 35.5 cm) 
WCP maximum.
Contact local gas supplier if you are not sure about the inlet 
(supply) pressure.
Burner Requirements for High Altitude
Input ratings shown on the model/serial rating plate are for 
elevations up to 2,000 ft (609.6 m).
For elevations above 2,000 ft (609.6 m), ratings are reduced at a 
rate of 4% for each 1,000 ft (304.8 m) above sea level. Orifice 
conversion is required. See “Assistance or Service” section to 
order.
Gas Supply Line Pressure Testing
Testing above ½ psi (3.5 kPa) or 14" (35.5 cm) WCP (gauge):
The Power™ burner and its individual shutoff valve must be 
disconnected from the gas supply piping system during any 
pressure testing of that system at test pressures greater than 
½ psi (3.5 kPa).
Testing below ½ psi (3.5 kPa) or 14" (35.5 cm) WCP (gauge) or 
lower:
The Power™ burner must be isolated from the gas supply piping 
system by closing its individual manual shutoff valve during any 
pressure testing of the gas supply piping system at test 
pressures equal to or less than ½ psi (3.5 kPa).
Gas Connection Requirements
20 lb LP Gas Fuel Tank
This Power™ burner is equipped for use with a 20 lb LP gas fuel 
tank (fuel tank not supplied). A gas pressure regulator/hose 
assembly is supplied.
It is also design-certified by CSA International for local LP gas 
supply or for Natural gas with appropriate conversion.
The 20 lb LP gas fuel tank must be mounted and secured.
Door Style Tank Tray
1. Open cabinet doors.
2. Pull out the tank tray.
3. Place the 20 lb LP gas fuel tank bottom collar into the 
mounting hole in the tank tray.
4. Tighten the locking screw against the bottom collar of the 
20 lb LP gas fuel tank to secure.
5. Slide tank tray back into the cabinet.
6. Close cabinet doors.
Local LP Gas Supply Conversion
Conversion must be made by a qualified gas technician. The 
qualified gas technician shall provide the gas supply to the 
selected Power™ burner location in accordance with the 
National Fuel Gas Code ANSI Z223.1/NFPA 54 - latest edition, 
and local codes. For conversion to local LP, the convertible 
regulator in the conversion kit supplied with the Power™ burner 
must be used.
IMPORTANT: The gas installation must conform with local 
codes, or in the absence of local codes, with the National Fuel 
Gas Code, ANSI Z223.1/NFPA 54 - latest edition. The qualified 
LP gas technician shall provide the LP gas supply to the selected 
Power™ burner location in accordance with the National Fuel 
Gas Code, ANSI Z223.1/NFPA 54 and local codes.
Follow instructions for converting to local LP gas in the “Gas 
Conversions” section.
A. Gas pressure regulator/hose assembly
A
Tank tray
A. Locking screw
B. Mounting hole
C. Bottom collar
A. New CSA International approved 
“outdoor” flexible gas supply line
B. Rear of Power™ burner
C. To local LP gas supply
A
B
C
B
C
A