Honeywell Bypass Drum Humidifier (HE120A) 설치 설명서

다운로드
페이지 48
HE120 BY-PASS DRUM HUMIDIFIER
13
69-1860EF—01
11.
Snap Humidifier Cover into place.
STEP 7: INSTALL DRAIN
CAUTION
Water Hazard. 
Can result in water damage to property. 
Install overflow drain in applications where water 
damage can result from Float Valve failure.
1.
Slide the 1/2 in. Overflow Clamp over the 3/8 in. inside 
diameter, 1/2 in. outside diameter Overflow Tube. 
See Fig. 30.
2.
Push the Overflow Tube over the Drain Fitting. 
3.
Hand-tighten the Clamp around the Overflow Tube and 
the Drain Fitting.
4.
Fasten the Overflow Tube (can use duct tape) along the 
route to the drain to prevent movement and ensure 
downward slope. 
5.
Cut Overflow Tube to length so the tubing terminates at 
the drain or bucket using a utility knife. 
Fig. 30. Installing overflow tube.
IMPORTANT
Overflow Tube must follow downward slope from 
Humidifier to drain for correct draining.
STEP 8: INSTALL SADDLE VALVE
CAUTION
Chemical Hazard. 
Can cause personal injury or equipment damage.
Do not use any line connected to an air conditioner. 
Do not use gas line.
IMPORTANT
Do not turn handle before or while installing the sad-
dle valve. Be sure the piercing lance does not pro-
trude beyond the rubber gasket. Failure to do this 
may damage piercing needle.
To prevent debris from clogging the Float Valve, do 
not install the saddle valve with the handle pointing 
toward the floor.
NOTE:
This saddle valve can be used with either copper or 
steel/brass pipe. Please refer to the correct instruc-
tions for your application.
Copper Pipe:
1.
Shut off the water. (Either hot or cold water and either 
hard or softened water can be used in the Humidifier.)
2.
Turn handle counter clockwise until piercing lance is 
below the rubber gasket. See Fig. 31.
Fig. 31. Positioning Saddle Valve for installation with 
Copper Pipe.
3.
Assemble saddle valve over copper tube using 
#10 x 1-3/4 in. machine screws. See Fig. 32.
Fig. 32. Installing Saddle Valve.
M20177
LANCE 
BELOW 
GASKET
M13631
M20175
SCREW DRIVER
WATER LINE