HE120, HE160 HUMIDIFIER INSTALLATION KIT
69-1571
6
INSTALLING HUMIDISTAT
Mounting Duct
1.
Apply the template to the duct location chosen for 
the humidistat. Make sure the template is level 
before drilling the holes.
2.
Refer to the template (provided with the H8909 
Humidistat Installation Instructions) to drill the con-
trol assembly opening and mounting holes for the 
H8908. 
3.
Remove the H8908 case from the base.
4.
Position the foam gasket on the H8908 base.
5.
Position the base on the duct with the arrow up.
6.
Secure the base to the duct using the four 
1 in. (25 mm) mounting screws provided with humi-
distat.
7.
Connect the low-voltage wires to the leads and 
replace the H8908 case. See Fig. 12.
NOTE:
For wall mounting instructions, see the H8908 
Installation Instructions.
Fig. 12. Humidistat base and rear view.
WIRING
CAUTION
Hazardous Voltage. 
Can cause personal injury or equipment 
damage.
Disconnect power supply before installing or 
servicing equipment.
IMPORTANT
All wiring must comply with applicable local 
code, ordinances and regulations.
Wire the humidifier motor, humidistat and transformer. 
See Fig. 13.
Fig. 13. Wiring the controls.
1.
Run the two-strand thermostat wire from the 
humidifier to the transformer, from the transformer 
to the humidistat.
2.
Cut lengths of thermostat wire to reach between 
components, leaving adequate wire at both ends 
for connections.
NOTE:
Transformer and humidistat can be wired in any 
order.
3.
At the humidifier, connect the black and white con-
ductors to the two motor leads.
4.
At the transformer, connect both black conductors 
to the two transformer terminals. Use a wire nut to 
connect the white conductors.
5.
At the humidistat, connect the black and white con-
ductors to the two humidistat terminals.
TESTING HUMIDIFIER OPERATION
Checklist
Humidifier is level.
Starter collar is secured with sheet metal screws.
Summer shut-off damper is open (in winter position).
Control wiring was reviewed using circuit diagram.
Transformer is plugged in.
Feed line has no kinks.
Overflow line slopes continuously down and ends at 
floor drain or bucket.
After installation use the following steps to check the 
humidifier operation:
1.
Turn on the power and the water supply.
NOTE:
For HE160, see Adjusting Water Level section.
2.
Verify that basin fills and float shuts off before 
water enters overflow tubing. 
3.
Turn the H8908 Humidity Control to On.
4.
Make sure that drum or disk turns.
5.
Check for leaks.
6.
Reset the H8908 Humidity Control to a comfortable 
setting for automatic operation.
M20179
WIRE SLOT
HUMIDISTAT WIRES
HUMIDISTAT BASE
REAR OF HUMIDISTAT
Humidity Control
Régulateur d'humidité
-20 ¡F
-10 ¡F
0 ¡F
+10 ¡F
+20 ¡F
Over 20 ¡F
15%
20%
25%
30%
35%
40%
HUMIDITY
SETTING
OUTDOOR
TEMPERATURE
-30 ¡C
-25 ¡C
-20 ¡C
-10 ¡C
-5 ¡C
Over 0 ¡C
M20224
TRANSFORMER
BLACK
WHITE
BLACK
WHITE
HUMIDIFIER
DRIVE
MOTOR
HUMIDISTAT