Troubleshooting
Problem
Recommended Troubleshooting Steps
ERV/HRV unit not running
1.   Verify polarization of electrical receptacle.
2.   Verify breaker in electrical box.
3.   Verify that the external control or mode selector are activated to 
call for ventilation.
4.   Unplug the unit and verify that the external control(s) are wired 
correctly to the wiring terminal block.
Air is too dry
1.   Increase humidity level on the dehumidistat.
2.   Switch ventilation mode from continuous to intermittent.
3.   Install a humidifier.
Air too humid
1.   Reduce the humidity level on the controller.
2.   Make sure that the clothes dryer is vented to the outdoors.
3.   Wait for outside temperature to change. For example, it can be 
very humid at times in the summer.
4.   Verify balancing of the ERV/HRV unit (see Balancing Steps on 
page 7).
LED on control panel remains 
green
If the LED light on the ERV/HRV control panel remains green, the 
motors do not energize, and the controls do not operate. This can 
indicate that the Polarization in the main AC outlet is inverted
CAUTION: Servicing the ERV/HRV unit with its electrical circuitry can cause 
personal injury. Always make sure that power to the unit is disconnected prior to 
making any connections. Failure to disconnect the power could result in electrical 
shock. Service should only be performed by a qualified service technician.