UV100E ULTRAVIOLET SYSTEMS
68-0262—06
8
TROUBLESHOOTING AND SERVICE
The Ultraviolet System has no field-serviceable parts. Bulb 
cleaning is recommended as routine maintenance quarterly or 
every three months. Bulb replacement is required when the 
LED on the front of the UV system is lighted solidly. See the 
Owner’s Guide for detailed procedural information.
If systems with an airflow sensor (UV100E1043 and 
UV100E2009 Air Treatment Systems), incorrectly identify 
airflow, the airflow sensor may be calibrated incorrectly. To 
recalibrate the sensor, remove power to the furnace or turn off 
the system and fan, wait ten minutes, and then resume normal 
furnace operation. Even if the lamp fails to turn off, the sensor 
was recalibrated during this operation.
If the internal temperature exceeds the ballast high-
temperature limit, the control continues to retry every three 
hours until the temperature is low enough to run correctly. An 
Enviracom fault message (when connected) sent after 72 
hours. If reset is pushed during this fault, the control tries to 
restart but cannot start until temperature returns to normal.
If the bulb(s) burns out, experiences low supply voltage 
(brownout) or has an internal catastrophic failure, the control 
continues to retry once every hour until the problem is 
corrected. An Enviracom fault message (when connected) is 
sent after 24 hours. If reset is pushed during this fault, the 
control tries to restart but cannot start until fault is corrected. 
To determine if a bulb is burned out or other problem exists, 
press the reset button briefly (one second). The bulb(s) should 
come on (as indicated by the illuminating lamp light indicator). 
Hold reset button longer only when replacing the bulb. 
MAINTENANCE
How You Can Maintain Your UV System
You should regularly clean your ultraviolet lamp to maintain 
peak effectiveness of your air treatment or surface treatment 
system. Replace the ultraviolet bulb when the LED status light 
on the front of your UV System is on steadily.
CAUTION
Personal Injury Hazard.
Power supply can cause electrical shock.
Disconnect power supply before cleaning or replacing 
ultraviolet bulb(s).
Do not open base unit or lamp handle; there are no
user-serviceable components inside.
CAUTION
Breakable Glass Hazard.
Can cause personal injury.
Be careful when inserting bulb(s) into lamp base.
Wear protective gloves when handling bulb(s).
Quarterly Bulb Cleaning
MERCURY NOTICE
This device contains mercury (less than 5 mg) in the 
sealed ultraviolet bulb(s). Do not place your used 
bulb(s) in the trash. Dispose of properly. 
Broken Bulb Cleanup. 
Do not use a household vacuum. 
Sweep debris into a plastic bag and dispose of 
properly.
Contact your local waste management authority for 
instructions regarding recycling and the proper disposal 
of old bulb(s).
Bulb cleaning is recommended as routine maintenance 
quarterly or every three months. Use the UV Bulb Cleaning 
Reminder Schedule, Fig. 10, to help you establish and track 
your regular cleaning schedule.
Fig. 10. UV bulb cleaning reminder schedule.
CAUTION
UV Lamp Burn Hazard.
Harmful to bare skin.
Can cause severe burns.
Disconnect power 15 minutes before removing 
ultraviolet bulb(s).
To clean your bulb:
1. Disconnect the power to your heating and cooling 
system.
2. Unplug or turn off power to your UV system and allow the 
bulb to cool for at least 15 minutes.
3. Rotate your lamp handle counterclockwise and gently 
pull the lamp handle to remove the bulb(s). See Fig. 11.
YEAR 
UV BULB CLEANING REMINDER SCHEDULE
, (year)
M13516A
J
F
M
A
M
J
J
A
S
O
N
D
INSTALLATION DATE: (month)