Rack Mounted 
The D9824 receiver  is a 1U unit with connector  access at the rear panel. The receiver 
is intended  for mounting  in a standard 19" rack with minimum  1U spacing between 
units to allow adequate ventilation/air  flow. 
The D9824 receiver  is vented  from front to back. Multiple  units can be stacked in a 
rack, provided  that adequate cooling  is available. 
 
Cooling 
The D9824 receiver  is cooled by the use of internal  fans. The air intake is from the 
front and the air outlet is on the rear. 
Note: Adequate cooling  must be provided  equaling  107 W (maximum) at 25°C per 
unit to avoid overheating. 
 
CAUTION: 
The inlet  air temperature  must  not exceed  50°C/122°F  at any time. 
 
 
Grounding 
You must ensure  that the unit is properly  connected  to ground  to meet safety and 
EMC requirements.  Before any other  connection  is made, the unit must be connected 
to a protected ground  terminal  as described  below: 
 
Via the three  wire power  cord of the AC power  supply. This connection  is 
mandatory. 
 
In addition, via the protective  ground  terminal on the rear panel of the unit. This 
connection  provides  additional protection of the equipment. 
 
Mounting the D9824 Receiver to a Rack 
1  Mount L-brackets in the rack to support each D9824 receiver  to be installed. 
2  Place the receiver  in its position in the rack. 
3  Mount the receiver  securely  to the rack by securing  the mounting  flanges to the 
rack using the four screws provided. 
4  Make sure the air outlet holes  on the back of the receiver  are not obstructed to 
allow air flow from the  front to the back of the chassis.