Cisco UCS C220 M4 NEBS Server Service Note
 
  Features Specific to the Cisco UCS C220 M4 NEBS Server
Installing a 1050 W DC Power Supply, UCSC-PSU2-1050DC
If you are using the 1050 W DC power supply, you connect power using a 3-wire cable with a keyed 
connector that plugs into a fixed power-input socket on the power supply. 
Caution
Before beginning this wiring procedure, turn off the DC power source from your facility’s circuit breaker 
to avoid electric shock hazard.
Step 1
Turn off the DC power source from your facility’s circuit breaker to avoid electric shock hazard.
Step 2
Wire the supplied 3-wire connector cable (CAB-48DC-40A-8AWG) to your facility’s DC power source.
Note
The supplied connector cable contains 8 AWG gauge wires. The recommended facility wire gauge is 
8 AWG. The minimum facility wire gauge is 10 AWG.
Step 3
Plug the supplied connector cable into the power input socket on the power supply. The connector is 
keyed to the socket so that the polarity is aligned correctly.
Step 4
Return power from your facility’s DC power source at the circuit breaker.
Figure 1-2
1050 W, –48 VDC Power Supply Connector 
NEBS Server Component Support
This NEBS server uses the small form-factor drives, eight-drive version of the Cisco UCS C220 M4 
server. For the list of supported components in the NEBS version of the server and their ordering PIDs, 
refer to the 
1
Keyed cable connector 
(CAB-48DC-40A-8AWG)
3
Power supply status LED
2
Keyed DC input socket
305145
1
2
3
1050W DC
+DC
- DC