Cisco Aironet Series Power Injector AIR-PWRINJ1500-2= Installation Instructions
 
  Grounding the Power Injector
d.
Use a screw driver to tighten the screw into the wall anchor.
Grounding the Power Injector
We recommend that you ground the power injector after installing it. To ground the power injector, 
follow these steps:
Step 1
Attach the wire to a UL listed ring lug, suitable for conductor size. Be sure to double crimp the 
connection.Attach the ring lug to a mounting tab on the power injector.
Note
Use a minimum 12 AWG or 2.5 mm cross-sectional area, 90
o
C, copper, green/yellow conductor 
for permanent ground connection.
Step 2
Attach other end of the wire to a permanent ground connection in the building installation.
Installing the Power Injector
To install the power injector, follow these steps:
Step 1
Plug a shielded outdoor rated Ethernet cable into the TO AP port on the power injector.
Warning
To reduce the risk of fire, use only No. 26 AWG or larger telecommunication line cord. 
Statement 1023
Note
To comply with FCC regulations, the length of Ethernet cable connecting the power injector to 
the access point cannot be less than 10 ft (3 m).
Step 2
Plug the other end of the Ethernet cable into the Ethernet Port on the access point.
Note
For detailed information about connecting the Ethernet cable to an access point, see the 
Hardware Installation Guide for that access point.
Step 3
Plug a shielded outdoor rated Ethernet cable into the TO SWITCH port on the power injector.
Warning
To reduce the risk of fire, use only No. 26 AWG or larger telecommunication line cord. 
Statement 1023
Step 4
Plug the other end of the Ethernet cable into your Ethernet switch, hub, or network.