Installing and connecting the drain hose of the indoor unit
When installing the drain hose for the indoor unit, check if condensation draining is adequate.   
When passing the drain hose through the 65-mm hole drilled in the wall, check the followings:
•   The hose will be 
 permanently into position after 
 the installation and the gas leak test; refer to page 
36 for further details. 
•   If you do not use the other drain hose hole, block it with a rubber stopper. 
•   Make sure the installed direction of the drain hose is correct. 
Inadequate installation may cause condensate water leakage.
•   If the drain hose is routed inside the room, insulate the hose so that dripping condensation does not damage the 
•   DO NOT WALL UP THE DRAIN HOSE CONNECTION ! 
Drain hose connection must be easy accessible and serviceable. 
1.  If necessary, connect the 2-meter extension drain hose to the drain hose.
2.  If you use the extension drain hose, insulate the inside of the extension drain hose with a shield.
3. 
tightly with a clamp.
4.  Pass the drain hose under the refrigerant pipe, keeping the drain hose 
tight.
5.  Pass the drain hose through the hole in the wall. Check if it slants 
downwards as seen in the picture. 
Drain hose installation
Shield
Drain hose
Extension drain hose
Wall
Indoor unit
Drain hose
The drain hose must  NOT 
slant upwards. 
The end of the drain hose 
must NOT be placed under 
water.
The drain hose must not 
be bent.
Keep a clearance of at least 
5cm between the end of the 
drain hose and the ground.
5cm
less
Do not place the end of the 
drain hose in a hollow.
Ditch
After completing the 
installation of the drain 
hose, pour water into 
the drain pan to check 
whether the hose is well 
drained.