Evacuating the indoor unit
1.  Make sure that you have all the required tools (pipe cutter, reamer, flaring tool and pipe holder).
2.  If you want to shorten the pipe, cut it using a pipe cutter, ensuring that the cut edge remains at 90° with the side of the 
pipe (see below examples of correct and incorrect cut edges).
3.  To prevent a gas leak, remove all burrs at the cut edge of the pipe using a reamer.
4.  Put a flare nut slightly into the pipe and modify the flare.
The indoor unit is supplied with inert gas  (nitrogen).
Before installing the unit, check if nitrogen gas flow out of indoor unit.
If this one isn’t true, DO NOT INSTALL THE UNIT since leakage could be inside the indoor unit. 
The length of the pipe can be:
 • Extended up to : see table page 29
 • Shorten up to: see page 29
If you need a pipe longer than 5 meters:
•  You must add refrigerant to the pipes; otherwise, the indoor unit may freeze.
Unscrew the caps
Pipes
Oblique
Rough
Burr
Pipe 
cutter
Pipe
•   The remaining air in the Refrigeration cycle, which contains moisture,
may cause malfunction on the compressor.
•   Always contact the service center or a professional installation agency
for product installation.
•   To prevent dirt or foreign substances from getting into the pipes during
installation, do NOT remove the caps completely until you are ready to 
connect the pipes.
Cutting or extending the pipe
Pipe
Flare
90°± 2°
°
±
°
5
4
R 0.4~0.8
B
•  Face the pipe down while removing the burrs to make sure that burrs do not get in to the pipe.
1.  Unscrew the caps at the end of each pipe. 
  All inert gas exhausts from the indoor unit.
Outer Diameter (D)
Depth (A)
Flaring Size (B)
ø6.35 mm
1.3 mm
8.7 - 9.1 mm
ø9.52 mm
1.8 mm
12.8 - 13.2 mm
ø12.70 mm
2.0 mm
16.2 - 16.6 mm
ø15.88 mm
2.2 mm
19.3 - 19.7 mm
MAX4 AR30JV&JS_IB&IM_DB68-04541A_EN.indd   36