Samsung AR24MVFSBWKXME 설치 가이드

다운로드
페이지 2
Installation manual
 
AR✴✴HVSS✴✴, AR✴✴JVFS✴✴, AR✴✴KVFS✴✴, AR✴✴KVFN✴✴,  
AR✴✴MVFS✴✴, AR✴✴MVFN✴✴
Safety Information on 
Installation
Carefully follow the precautions listed below because 
they are essential to guarantee the safety of both the air 
conditioner and the workers.
•  Always disconnect the air conditioner from the power 
supply before servicing it or accessing its internal 
components. 
•  Verify that installation and testing operations are 
performed by qualified personnel. 
•  Verify that the air conditioner is not installed in an easily 
accessible area. 
General information
•  Carefully read the content of this manual before installing 
the air conditioner and store the manual in a safe place in 
order to be able to use it as reference after installation. 
•  For maximum safety, installers should always carefully 
read the following warnings. 
•  Store the operation and installation manual in a safe 
location and remember to hand it over to the new owner if 
the air conditioner is sold or transferred. 
•  This manual explains how to install an indoor unit with a 
split system with two SAMSUNG units. The use of other 
types of units with different control systems may damage 
the units and invalidate the warranty. The manufacturer 
shall not be responsible for damages arising from the use 
of non compliant units. 
•  This product has been determined to be in compliance 
with the Low Voltage Directive (2006/95/EC) and the 
Electromagnetic Compatibility Directive (2004/108/EC) of 
the European Union.
•  The manufacturer shall not be responsible for damage 
originating from unauthorised changes or the improper 
connection of electric and requirements set forth in the 
“Operating limits” table, included in the manual, shall 
immediately invalidate the warranty. 
•  The air conditioner should be used only for the applications 
for which it has been designed: the indoor unit is not 
suitable to be installed in areas used for laundry.  
•  Do not use the units if damaged. If problems occur, switch 
the unit off and disconnect it from the power supply.
•  In order to help prevent electric shocks, fires or injuries, 
always stop the unit, disable the protection switch and 
contact SAMSUNG’s technical support if the unit produces 
smoke, if the power cable is hot or damaged or if the unit 
is very noisy. 
•  Always remember to inspect the unit, electric connections, 
refrigerant tubes and protections regularly. These 
operations should be performed by qualified personnel 
only. 
•  The unit contains moving parts, which should always be 
kept out of the reach of children. 
•  Do not attempt to repair, move, alter or reinstall the unit. 
If performed by unauthorised personnel, these operations 
may cause electric shocks or fires. 
•  Do not place containers with liquids or other objects on 
the unit. 
•  All the materials used for the manufacture and packaging 
of the air conditioner are recyclable. 
•  The packing material and exhaust batteries of the remote 
control (optional) must be disposed of in accordance with 
current laws. 
•  The air conditioner contains a refrigerant that has to be 
disposed of as special waste. At the end of its life cycle, the 
air conditioner must be disposed of in authorised centres 
or returned to the retailer so that it can be disposed of 
correctly and safely.
Installation of the unit
•  IMPORTANT: When installing the unit, always remember 
to connect first the refrigerant tubes, then the electrical 
lines. Always disassemble the electric lines before the 
refrigerant tubes. 
•  Upon receipt, inspect the product to verify that it has not 
been damaged during transport. If the product appears 
damaged, DO NOT INSTALL it and immediately report 
the damage to the carrier or retailer (if the installer or the 
authorised technician has collected the material from the 
retailer.) 
•  After completing the installation, always carry out a 
functional test and provide the instructions on how to 
operate the air conditioner to the user. 
•  Do not use the air conditioner in environments with 
hazardous substances or close to equipment that release 
free flames to avoid the occurrence of fires, explosions or 
injuries. 
•  Our units must be installed in compliance with the spaces 
indicated in the installation manual to ensure either 
accessibility from both sides or ability to perform routine 
maintenance and repairs. The units’ components must be 
accessible and that can be disassembled in conditions of 
complete safety either for people or things. For this reason, 
where it is not observed as indicated into the Installation 
Manual, the cost necessary to reach and repair the unit 
(in safety, as required by current regulations in force) with 
slings, trucks, scaffolding or any other means of elevation 
won’t be considered in-warranty and will be charged to 
end user.
•  When installing the outdoor unit at the seaside, make 
sure that it is not directly exposed to sea breeze. If you 
cannot find an adequate place free from direct sea breeze, 
construct a protection wall or a protective fence.
 
Install the outdoor unit in a place (such as near buildings 
etc.) where it can be protected from sea breeze. Failure to 
do so may cause a damage to the outdoor unit.
Sea
Sea breeze
Outdoor unit
Outdoor unit
Sea breeze
Sea
•  If you cannot avoid installing the outdoor unit at the seaside, 
construct a protection wall around to block the sea breeze.
•  Construct a protection wall with a solid material such as 
concrete to block the sea breeze. Make sure that the height 
and the width of the wall are 1.5 times larger than the size 
of the outdoor unit. Also, secure a space larger than 600 
mm between the protection wall and the outdoor unit for 
exhausted air to ventilate.
Sea
Sea breeze
Outdoor unit
Protection wall
Outdoor unit
Protection wall
•  Install the unit in a place where water can drain smoothly.
•  If you have any difficulty finding installation location as 
prescribed above, contact your manufacturer for details.
•  Be sure to clean the sea water and the dust on the heat 
exchanger of the outdoor unit and apply a corrosion inhibitor 
on it. (At least once in a year.)
Power supply line, fuse, or circuit 
breaker
•  Always make sure that the power supply is compliant with 
current safety standards. Always install the air conditioner in 
compliance with current local safety standards. 
•  Always verify that a suitable grounding connection is 
available. 
•  Verify that the voltage and frequency of the power supply 
comply with the specifications and that the installed power 
is sufficient to ensure the operation of any other domestic 
appliance connected to the same electric lines. 
•  Always verify that the cut-off and protection switches are 
suitably dimensioned. 
•  Verify that the air conditioner is connected to the power 
supply in accordance with the instructions provided in the 
wiring diagram included in the manual. 
•  Always verify that electric connections (cable entry, section 
of leads, protections…) are compliant with the electric 
specifications and with the instructions provided in the 
wiring scheme. Always verify that all connections comply 
with the standards applicable to the installation of air 
conditioners.
•  Be sure not to perform power cable modification, extension 
wiring, and multiple wire connection.
 
It may cause electric shock or fire due to poor connection, 
poor insulation, or current limit override.
 
When extension wiring is required due to power line 
damage, refer to "Step 2.4 Optional: Extending the power 
cable" in the installation manual.
Preparation
Step 1.1  Choosing the installation 
location
Overview of installation location requirements
100 mm or more
Outdoor 
Unit
Indoor Unit
Cut insulation to have 
rainwater drained
Outer wall
Drain hose hole
You can select the direction of 
draining (left or right). 
Maximum pipe height: 15 m
Maximum pipe length: 30 m
125 mm or 
more
125 mm or 
more
The actual units may look different from the 
images depicted here.
Make a U-trap (A) on the pipe 
(which is connected to the indoor 
unit) at outer wall and cut the 
bottom part of the insulation 
(about 10 mm) to prevent 
rainwater from getting inside 
through the insulation. 
Make at least one round to reduce 
noise and vibration.
CAUTION
  CAUTION
•  Comply with the length and height limits described in the 
figure above.
Minimum clearances for the outdoor unit
Wall
Minimum clearance in mm
300
600
Air flow direction
Side view
Top view
When installing 1 outdoor unit                                        (6 cases)
(Unit: mm)
300
1500 
300
150
600
1500
2000 
500 
300 
300
 
1500
 (Unit : m)
Model
Pipe length
Pipe height
Minimum
Maximum
Maximum
✴✴
09/12✴✴ME/TC
✴✴
10/13✴✴UN
3
15
7
✴✴
09/12✴✴SS
3
15
8
✴✴
18/24✴✴ME/UN
3
20
12
✴✴
18/24✴✴SS/TC
3
30
15
When installing more than 1 outdoor unit                  (5 cases)
(Unit: mm)
1500
600
3000
200
3000
300
1500
600
600
1500
300
300
600
600
600
500 
300
500
300
  CAUTION
•  If the outdoor unit is installed with any insufficient 
clearance, it may generate sound and affect the whole 
product.
•  Be sure to install the outdoor unit in a level place where its 
vibration does not affect the whole product.
Step 1.2  Unpacking
Unpacking the indoor unit
1  Open the indoor unit package. 
2  Remove the left and right cushions. 
3  Pull out the unit from the package. 
Unpacking the outdoor unit
1  Remove the package. 
2  Remove the top cushion. 
3  Pull out the unit from the bottom cushion. 
Step 1.3  Checking and preparing 
accessories and tools
Accessories
Accessories in the indoor unit package
Installation plate (1)
✴✴
10✴✴UN
Installation plate (1)
✴✴
13/18✴✴UN
Installation plate (1)
✴✴
09/12✴✴
✴✴
18✴✴ME
Installation plate (1)
✴✴
18✴✴SS/TC
✴✴
24✴✴
Remote control (1)
Remote control holder (1)
Remote control battery (2)
Users Manual (1)
Installation Manual (1)
Cap screw (2)
Installation Manual (1)
Optional accessories
Insulated assembly pipe,  
Ø 6.35 mm (1)
Insulated assembly pipe,  
Ø 9.52 mm (1)
✴✴
09/10/12/13✴✴
Insulated assembly pipe,  
Ø 12.70 mm (1)
✴✴
18✴✴
Insulated assembly pipe,  
Ø 15.88 mm (1)
✴✴
24✴✴
Drain Hose, 2 m long (1)
Pipe clamp B (3) 
Pipe clamp A (3)
Vinyl tape (2)
PE T3 foam tube insulation (1)
Putty 100 g (1) 
Drain plug (1)
M4 x 25 tapped screw (6)
Cement nail (6)
4-wire assembly cable (1)
✴✴
09/12✴✴TC
✴✴
09/12/18✴✴ME
✴✴
10/13/18✴✴UN
3-wire power cable (1)
✴✴
18/24✴✴TC
✴✴
09/12/18/24✴✴SS
3-wire assembly cable (1)
✴✴
18/24✴✴TC
✴✴
24✴✴ME/UN
✴✴
09/12/18/24✴✴SS
2-wire assembly cable (1)
✴✴
18/24✴✴TC
✴✴
09/12/18/24✴✴SS
1-wire assembly cable (1)
✴✴
24✴✴ME/UN
Accessories in the outdoor unit package
Rubber leg (4)
  NOTE
•  A flare nut is attached to the end of each pipe of an 
evaporator or a service port. Use flare nuts when connecting 
the pipes.
•  Wire assembly cables are optional. If they are not supplied, 
use standard cables.
•  The drain plug and the rubber legs are included only when 
the air conditioner is supplied without assembly pipes. 
•  If these accessories are supplied, they are in the accessory 
package or outdoor unit package.
Tools 
General tools
•  Vacuum pump  
(Backward flowing 
prevention)
•  Manifold gauge
•  Stud finder
•  Torque wrench
•  Pipe cutter
•  Reamer
•  Pipe bender
•  Spirit level
•  Screwdriver
•  Spanner
•  Drill
•  L-wrench
•  Measuring tape
Tools for test operation
•  Thermometer
•  Resistance meter
•  Electroscope
Step 1.4  Drilling a hole through the 
wall
Before fixing the installation plate to a wall and then fixing 
the indoor unit to the installation plate, a window frame, or 
a gypsum board, you must determine the position of a hole 
(with 65 mm inner diameter) through which the pipe bundle 
(consisting of power and communication cables, refrigerant 
pipes, and drain hose) will pass and then drill that hole.
1  Determine the position of a 65 mm hole in consideration 
of the possible directions of the pipe bundle and the 
minimum distances between the hole and the installation 
plate.
Right
Left
Rear right or left
<Possible directions of the pipe bundle>
Bottom right
  CAUTION
•  If changing the pipe direction from left to right, do not 
drastically bent it but slowly turn it in the opposite 
direction as shown. Otherwise, the pipe may be damaged 
in the process.
<Minimum distances between the hole and the 
installation plate>
Pipe bundle hole
2  Drill the hole.
  CAUTION
•  Be sure to drill only one hole. 
•  Make sure that the hole slants downwards so that the 
drain hose slants downwards to drain water well.
Wall
Drain hose
Indoor unit
<The hole slants downwards>
Step 1.5  Taping the pipes, cables, and 
drain hose
1  Wrap foam insulation on parts without insulation on the 
ends of the refrigerant pipes, as shown in the figure. This 
wrapping minimises condensation problem. 
Insulation
Refrigerant pipes
2  Wind the refrigerant pipes, power cable, 
communication cable and drain hose with vinyl 
tape to make a pipe bundle. 
Refrigerant pipes 
(assembly pipe)
Installation plate
Vinyl tape
Drain hose
Power and communication cables 
(assembly cable)
Indoor Unit Installation
Please scan this QR code for detail 
video of indoor unit installation.
Step 2.1  Disassembling the cover 
panel
1  Remove the cap screws, then the screws. 
 (Unit : mm)
Model
A
B
C
D
✴✴
10✴✴UN
36
60
65
36
✴✴
09/12✴✴
✴✴
13✴✴UN
36
120
81
36
✴✴
18✴✴ME/UN
36
190
81
36
✴✴
18✴✴TC/SS
✴✴
24✴✴
33
110
110
33
Pipe bundle hole: Ø 65 mm
Cap screw
Screw
Phillips screwdriver
Flat-head screwdriver
2  Unlock the side hooks ( ,  ), then centre hooks ( ). 
Then unlock the bottom hooks ( ) to pull out the cover 
panel. 
B
B
C
A
A
Centre hook (A)
Bottom/Side hook (B/C)
1
2
4
Step 2.2  Disassembling the 
installation plate
Step 2.3  Connecting the power and 
communication cables (assembly 
cable)
Control box
1(L)2(N)
F1 F2
•  When performing electrical and earthing works, be sure 
to comply with the 'technical standards of electrical 
installations' and the 'wiring regulations' in the local 
regulations.
•  Tighten the terminal block screw to 1.2-1.8 N•m (1.2-1.8
kgf•cm).
  NOTE
•  Each wire is labelled with the corresponding terminal 
number.
•  Use shield cable (Category 5; less than 50pF/m) for noisy 
environmental site.
•  Power supply cords of parts of appliances for outdoor 
use shall not be lighter than polychloroprene sheathed 
flexible cord. (Code designation IEC: 60245 IEC66/CENELEC: 
H07RN-F, IEC: 60245 IEC57/CENELEC: H05RN-F, IEC: 60227 
IEC53/CENELEC: H05VV-F)
•  Power & Communication cable shall not exceed 30m.
  CAUTION
•  For the terminal block wiring, use a wire with a ring terminal 
socket only. Regular wires without a ring terminal socket 
may become a hazard due to overheating of the electrical 
contact during installation.
•  If you need to extend the pipe, be sure to extend the cable, 
too. The maximum length of each of the cable and pipe 
used should not exceed 15 meters (✴✴09/12/18✴✴) and 20 
metres (✴✴24✴✴).
•  Do not connect two or more different cables to extend the 
length. This connection may cause fire.
•  Each circular terminal must match the size of its 
corresponding screw in the terminal block.
•  After connecting the cables, make sure that terminal 
numbers on the indoor and outdoor units match.
•  Ensure that power and communication cables are 
separated, they must not be in the same cable.
  WARNING
•  Connect the wires firmly so that wires cannot be pulled 
out easily. (If they are loose, it could cause burn-out of the 
wires.)
Step 2.4  Optional: Extending the 
power cable 
1  Prepare the following tools.
Tools
Spec
Shape
Crimping 
pliers
MH-14
Connection 
sleeve (mm)
20xØ6.5 (HxOD)
Insulation 
tape
Width 19 mm
Contraction 
tube (mm)
70xØ8.0 (LxOD)
2  As shown in the figure, peel off the shields from the rubber 
and wire of the power cable.  
•  Peel off 20 mm of cable shields from the pre-installed 
tube.
  CAUTION
•  For information about the power cable specifications for 
indoor and outdoor units, refer to the installation manual.
•  After peeling off cable wires from the pre-installed tube. 
Insert a contraction tube.
Before 
connecting
Correct
Upside 
down
Damaged
Non-
circular
After 
connecting
Correct
Correct
Upside 
down
Non-fitted
(Front view) (Side view)
<Circular terminal>
Power cable
Pre-installed tube for the power cable
(Unit: mm)
(Unit: mm)
20
20
20
20
60
120
180
3  Insert both sides of core wire of the power cable into the 
connection sleeve. 
•  Method 1: Push the core wire into the sleeve from both 
sides.
•  Method 2: Twist the wire cores together and push it into 
the sleeve.
Connection sleeve
Connection sleeve
Method 1
Method 2
4  Using a crimping tool, compress the two points and flip it over 
and compress another two points in the same location.
•  The compression dimension should be 8.0.
Compression 
dimension
•  After compressing it, pull both sides of the wire to make 
sure it is firmly pressed.
Compress it 4 times.
5 mm
Compress it 4 times.
5 mm
Method 1
Method 2
5  Wrap it with the insulation tape twice or more and 
position your contraction tube in the middle of the 
insulation tape.  
Three or more layers of insulation are required.
Method 1
Method 2
Insulation tape
40 mm
35 mm
Insulation tape
6  Apply heat to the contraction tube to contract it.
Contraction tube
7  After tube contraction work is completed, wrap it with the 
insulation tape to finish.
Insulation tape
  CAUTION
•  Make sure that the connection parts are not exposed to 
outside.
•  Be sure to use insulation tape and a contraction tube made 
of approved reinforced insulating materials that have the 
same level of withstand voltage with the power cable. 
(Comply with the local regulations on extensions.)
  WARNING
•  In case of extending the electric wire, please DO NOT use a 
round-shaped pressing socket.
 
Incomplete wire connections can 
cause electric shock or a fire. 
DB68-06570B-00
N(1) 1
2
✴✴
09/12✴✴TC
✴✴
10/13/18/24✴✴UN
✴✴
09/12/18/24✴✴ME
✴✴
09/12/18/24✴✴SS
✴✴
18/24✴✴TC
Fasten the screws for the wire holders.
Model
✴✴
09/12✴✴ME/TC
✴✴
10/13✴✴UN
✴✴
18✴✴ME/UN
✴✴
24✴✴ME/UN
Power cable  
(Indoor unit)
3G X 1.0 mm², 
H05VV-F
3G X 1.5 mm², 
H05VV-F
3G X 2.5 mm², 
H05VV-F
Indoor-to-
Outdoor power 
cable
4G X 1.5 mm², 
H07RN-F
4G X 1.5 mm², 
H07RN-F
3G X 1.0 mm², 
H07RN-F
1 X 0.75 mm², 
H05RN-F
Type GL
20 A
25A
25A
Model
✴✴
09/12✴✴SS
✴✴
18/24✴✴SS/TC
Power cable  
(Outdoor unit)
3G X 2.5 mm², H07RN-F
Outdoor-to-
Indoor power 
cable
3G X 1.0 mm², H07RN-F
Communication 
cable
2 X 0.75 mm², H05RN-F
Type GL
20 A
25 A
IM_TC_INV.indd   1
12/22/2016   12:57:52 PM