Samsung ASV18PSMN 사용자 설명서

다운로드
페이지 48
41
Purging the connected pipes
Refrigerant type
GWP value
R410A
1975
GWP=Global Warming Potential
Indoor unit
Outdoor unit
= ( 
) kg
= ( 
) kg
+
= ( 
) kg
 
covered by the Kyoto Protocol.
a
c
d
b
Protocol.  
Do not vent gases into the atmosphere.
1. 
  
 
 the factory refrigerant charge of the product, 
  
   
  
   
+
 the total refrigerant charge. on the refrigerant charge label 
supplied with the product.
R410A is a mixed type of refrigerant. It is necessary for recharging under conditions of liquid. When recharging refrigerant from 
the refrigerant cylinder to the equipment, follow the instructions below. 
1.  Before recharging, check whether the cylinder has a siphon or not. 
There are two ways to recharge the refrigerant.
Important information regulation regarding the refrigerant used
Charging the refrigerant under conditions of liquid by using a liquid pipe
a.   
Factory refrigerant charge of the product:  
see unit name plate
b.   
to the above information for the quantity of refrigerant 
replenishment.)
c.  Total refrigerant charge
d.   Refrigerant cylinder and manifold for charging
•   The 
 label must be adhered in the proximity of the product charging port (e.g. onto the inside of the stop 
valve cover).
Cylinder with siphon
siphon
  Charge the refrigerant standing the 
cylinder upright.
Cylinder without siphon
  Charge the refrigerant turning the cylinder 
upside down.
•   If R410A refrigerant is charged with gas, the composition of the charged refrigerant changes and the 
characteristics of the equipment vary.
•   During the measuring operation of refrigerant quantity added use an electronic balance.  
If cylinder doesn’t have syphon, upset it.