Samsung AR13FVSEDUUN 사용자 설명서

다운로드
페이지 48
36
Installing and connecting the assembly pipe of the indoor unit
1.  Cut out the appropriate knock-out piece (A, B, C) on the rear of the indoor 
unit unless you connect the pipe directly from the rear.     
2.  Smooth the cut edges.
3.  Remove the protection caps of the pipes and connect the assembly pipe 
torque wrench, applying the following torque: 
4. 
5. 
 
Then pull it out through the appropriate hole.
  
  The pipe should not project from the rear of the indoor unit.
  
  The bending radius should be 100 mm or more.  
6.  Pass the pipe through the hole in the wall. 
7.  For further details on how to connect to the outdoor unit and purge the air, refer to page 40.
refrigeration grade pipe only, (Cu DHP type according to ISO1337), degreased and deoxidized, suitable for operating pressures 
of at least 4200 kPa and for burst pressure of at least 20700 kPa. Under no circumstances must sanitary type copper pipe be 
used. 
There are 2 refrigerant pipes of 
 diameters:
 
• 
 
The smaller one is for the liquid refrigerant
 
• 
 
The larger one is for the gas refrigerant
 
need to extend the pipe using the assembly pipe (optional).
The connection procedure for the refrigerant pipe varies  
according to the exit position of the pipe when facing the wall:
 
• 
 
Right(A)
 
• 
 
Left(B)
 
• 
 
Underside(C)
 
• 
 
Rear
B
A
C
•  If you want to shorten or extend the pipes, refer to page 37~38.
•   Tighten the 
 nut with torque wrench according to 
 method. 
•   DO NOT WALL UP THE PIPE CONNECTION ! 
All refrigerant pipe connection must be easy accessible and serviceable.
•   The pipe will be insulated and 
 permanently into position after 
 the installation and the gas leak test; 
refer to page 44 for further details.
MAX_XSA_IBIM_DB98-33747A_E.pdf
Outer Diameter
Torque
N•m
(kgf•cm)
ø6.35 mm
14 ~ 18
140 ~ 180
ø9.52 mm
34 ~ 42
350 ~ 430
ø12.70 mm
49 ~ 61
500 ~ 620
ø15.88 mm
68 ~ 82
690 ~ 830