Please  shut  down  the  entire  system  again  if  you 
cannot  solve  a  problem  that  occurs.  To  do  this, 
press the OFF pushbutton for approx. 2 seconds. 
Disconnect the UPS from the mains  by  actuating 
the  mains  input  miniature  circuit  breaker  (no. 2, 
p. 26/27). Please contact our hotline (see p. 4).
8.
When  the  displays  are  correctly  lit  as  described, 
switch  on  your  loads  one  after  the  other.  When 
doing this, take care not to exceed the maximum 
permitted load capacity of the UPS.
6.1
Operating Modes
The following operating modes are distinguished:
Operation with mains supply (6.1.1)
Operation with faulty mains supply (6.1.2)
Operation with faulty inverter (6.1.3)
Manual bypass (6.1.4)
6.1.1
Normal Operation
Battery
Load 
REC
REC
INV
Manual 
bypass
Manual bypass path
SBS
Mains input 
miniature circuit 
breaker
Main
s
Schematic 
diagram
Secured 
busbar
Load
Power circuit with 
mains supply
Once  you  have  connected  the  UPS  to  a  suitable  mains 
connection,  you  can  start  operation  using  the  UPS  main 
switch.  Normally,  the  UPS  operates  continuously.  The  UPS 
now supplies the output with voltage, which is signalled by the 
mains  symbol  (Line  LED)  and  the  inverter  symbol  (Inverter 
LED) being lit.
This  operating  mode,  generally  referred  to  as  “online”  mode, 
ensures  the  greatest  protection,  in  particular  when  there  are 
mains fluctuations  and  mains  failures,  because  the  loads  are