eaton corporation ePDU Industrial Products Catalog
14
CABLE ASSEMBLY OPTIONS:
CBL113: 10/5 cable 9’ long terminated with a NEMA L21-30P at 
one end and a mating IEC 60309 connector at the other end.
For use in North America at 120/208V~
CBL114: 5x4.0 mm harmonized cable 9’ long with an
IEC 60309 connector at both ends.  
For use in Europe at 230/400V~
This system is designed to be controlled Locally or  
Remotely via a remote control panel (refer to pages 16-17).
Three-Phase Systems-International PC2672 Series
120/208V~ OR 230V/400V~, Three-Phase WYE, 30A, 50/60 Hz
RACK MOUNTED
•  19” x 5.25” (3U) x 16.5” with recess
 mounting
•  Approximate shipping weight: 41 lb.
POWER INPUT
•  5’ power cable with IEC 309 plug is
 attached to unit through the front panel
 cable grip
•  Unit ships with mating connector to
 IEC 60309 outlets on front panel
EMI/RFI FILTERING
•  Common Mode - line to ground
•  Differential Mode - line to line
•  Refer to Chart 9 on page 20
(17) IEC OUTLETS
(12) C13 Type:
•  120/208V Input, the output is 120V
•  230/400V input, the output is 230V
(4) C19 Type:
•  120/208V input, the output is 208V
•  230/400V input, the output is 230V
(1) IEC 309 3-Phase/30A:
•  120/208V input, the output is 120/208V
•  230/400V input, the output is 230/400V
(3) INDICATOR LIGHTS
•  Power “on” to PH-X, -Y, -Z
BRANCH CIRCUIT PROTECTION
•  UL489 Listed Main Disconnect breakers,
 with a long time delay curve, provide
 manual on/off switching and automatically
 trip with an overload condition
(4) REMOTE I/O PORTS
•  2 Front / 2 Rear: one on each side is
 sequence and the other is for remote
 on/off and EPO control. The PC2672 is
 controlled remotely only
•  Latching remote - (N/C) EPO between
 pins 2 & 3, momentary start between
 pins 1 & 3
SPECIFICATIONS
PC2672
Voltage Selectable Input Three Phase (50/60 Hz)
120/208V~ or 230/400V~
Voltage Output Single Phase on C13s (50/60 Hz)
120V~ or 230V~
Voltage Output Single Phase on C19s (50/60 Hz)
208V~ or 230V~
Voltage Output Three Phase on IEC 309 (50/60 Hz)
120/208V~ or 230/400V~
Current Input 
Per Phase
30A
Current Output 
Per Phase
24A
Full Load VA 
Per Phase
2880 VA at 120/208V or 5520 VA at 230/400V
Main Listed Breaker
30/30/30A
Secondary Listed Breakers, (1) Each For The C19 Outlets
(4) 16/16A
Secondary Listed Breakers, (1) Each For A Pair of C13 Outlets
(6) 10A
IEC 60320 Type C13 Outlets
(12) 15A/125V or 10A/250V
IEC 60320 Type C19 Outlets
(4) 20A/125V or 16A/250V
IEC 309 Outlet
(1) 3-phase/30A
EMI/RFI Filter
30A
Power Cord/Length/Plug
10/5, 5’, IEC 60309 3P+N+PE, 30A
VOLTAGE SELECTABLE