Toshiba ASD-G9ETH 사용자 설명서

다운로드
페이지 106
 
  
102
ICC 
BO4 ...... Resets the drive when it is faulted.  ASD parameter FA06, bit#13. 
BO5 ...... Enables or disables process (PID) feedback control.  Note that this 
object does not activate (turn on) feedback control.  It only enables or 
disables feedback control once it has already been activated.  ASD 
parameter FA06, bit#5. 
BO6 ...... Communication interface frequency priority selection.  Allows the 
frequency command from the interface card to be used by the drive 
without having to set the Frequency Mode parameter.  Refer to the 
Toshiba documentation regarding "Command Mode and Frequency 
Mode Control" for detailed information pertaining to the frequency 
source hierarchy and the use of overrides.  ASD parameter FA06, 
bit#14. 
BO7 ...... Communication interface command priority selection.  Allows 
commands (BO1, BO2, and BO5) from the interface card to be used 
by the drive without having to explicitly set the Command Mode 
parameter.  Refer to the Toshiba documentation regarding "Command 
Mode and Frequency Mode Control" for detailed information pertaining 
to the command source hierarchy and the use of overrides.  ASD 
parameter FA06, bit#5. 
BO8 ...... Output terminal data out 1.  Any programmable output terminals that 
are configured to output “specified data output 1” will follow the value 
of this BO.  ASD parameter FA50, bit#0. 
BO9 ...... Output terminal data out 2.  Any programmable output terminals that 
are configured to output “specified data output 2” will follow the value 
of this BO.  ASD parameter FA50, bit#1. 
BO10 .... Output terminal data out 3.  Any programmable output terminals that 
are configured to output “specified data output 3” will follow the value 
of this BO.  ASD parameter FA50, bit#2. 
  
  
Analog Input Objects 
 
AI1........ Output frequency in 0.01Hz units.  ASD parameter FD00. 
AI2........ Load current in 0.01% units (10000=100.00%=drive's rated current).  
ASD parameter FE03. 
AI3........ Output voltage in 0.01% units (10000=100.00%=drive's rated voltage).  
ASD parameter FE05. 
AI4........ Input power consumption (drive+motor) in 0.01kW units.  ASD 
parameter FE29. 
AI5........ Indicates the signal level currently being applied to the ASD's RR 
analog input terminal.  This can be used to monitor such items as 
feedback sensor outputs and other process variables.  Expressed in 
0.01% units (10000=100.00%=input rated value).  ASD parameter 
FE35.