Allen-Bradley Drive Fault Codes (continued)
Fault
Description
Corrective Action
Remarks
39
Phase V Fault
Phase to ground fault detected
between controller and motor in
Phase V.
between controller and motor in
Phase V.
Check wiring between the drive and motor. Check for
grounded phase.
grounded phase.
40
Phase W Fault
Phase to ground fault detected
between controller and motor in
Phase W.
between controller and motor in
Phase W.
Check wiring between the drive and motor. Check for
grounded phase.
grounded phase.
41
UV Short Fault
Excessive current has been
detected between two controller
output terminals.
detected between two controller
output terminals.
Check motor and external wiring to the controller output
terminals for shorted condition.
terminals for shorted condition.
42
UW Short Fault
Excessive current has been
detected between two controller
output terminals.
detected between two controller
output terminals.
Check motor and external wiring to the controller output
terminals for shorted condition.
terminals for shorted condition.
43
VW Short Fault
Excessive current has been
detected between two controller
output terminals.
detected between two controller
output terminals.
Check motor and external wiring to the controller output
terminals for shorted condition.
terminals for shorted condition.
57
Ground Warning
A current path to ground in excess
of 2A has been detected at one or
more of the drive output terminals.
of 2A has been detected at one or
more of the drive output terminals.
Check motor and external wiring to drive output terminals
for a grounded condition.
for a grounded condition.
48
Reset to Default Values
Parameters were reset to the
factory default values.
factory default values.
Verify and re-load the desired parameters.