Table 45 
Table 45 (continued)
Allen-Bradley Drive Fault Codes (continued)
Fault
Description
Corrective Action
Remarks
39
Phase V Fault
Phase to ground fault detected 
between controller and motor in 
Phase V.
Check wiring between the drive and motor. Check for 
grounded phase.
40
Phase W Fault
Phase to ground fault detected 
between controller and motor in 
Phase W.
Check wiring between the drive and motor. Check for 
grounded phase.
41
UV Short Fault
Excessive current has been 
detected between two controller 
output terminals.
Check motor and external wiring to the controller output 
terminals for shorted condition.
42
UW Short Fault
Excessive current has been 
detected between two controller 
output terminals. 
Check motor and external wiring to the controller output 
terminals for shorted condition.
43
VW Short Fault
Excessive current has been 
detected between two controller 
output terminals. 
Check motor and external wiring to the controller output 
terminals for shorted condition.
44
IPM Current Fault
Internal power module overcurrent 
limit exceeded.
Check for short circuit at the drive output or excessive load 
conditions at the motor, specifically cable capacitance to 
ground.
45
IPM Overtemp Fault
Internal power module thermal 
limit exceeded.
Check for blocked or dirty heatsink fins. Check ambient 
air. Check fan operation or filter blockage.
48
Reset to Default Values
Parameters were reset to the 
factory default values.
Verify and re-load the desired parameters.