PVI Industries nickelshield tank series 사용자 설명서

다운로드
페이지 1
Product is patented in the U.S., Canada, and Mexico. 
 
PVI INDUSTRIES, LLC 
FORT WORTH, TEXAS 76111 
PV 6299  03/04
 
(800) 784-8326  
•  www.pvi.com 
MAXIM• PACKAGED OIL WATER HEATER
 
NICKELSHIELD
®
  NICKEL-PLATED STORAGE TANK 
250 GALLON TANK SERIES 
 
MODEL NUMBER 
27N250A-MXO 40N250A-MXO
54N250A-MXO 72N250A-MXO
100N250A-MXO 120N250A-MXO
140N250A-MXO
 
GPH Recovery at 40° to 120° F 
340 
500 
670 
900 
1250 
1500 
1750 
 
GPH Recovery at 40° to 140° F 
270 
400 
540 
720 
1000 
1200 
1400 
 
Input 
Btu/h 
270,000  399,000  540,000  720,000  1,000,000 1,200,000 1,400,000 
 
Input, gph #2 Fuel Oil 
2.0 
2.8 
3.8 
5.0 
7.1 
8.6 
10.0 
A  Cold Inlet - NPT 
B  Hot Outlet - NPT 
Drain 
NPT 
1 1 1 1 1 1 1 
D  I - Beam Skids 
3 X 45 
3 X 45 
3 X 45 
3 X 45 
3 X 45 
3 X 45 
3 X 45 
Overall 
Height 
75 75 82 82 82 82 82 
Flue 
Outlet 
Diameter 
6  7  8 10 10 12 12 
H  Oil Inlet - NPT 
1/2 
1/2 
1/2 
1/2 
1/2 
1/2 
1/2 
Motor HP  120 V, 1Ø, 60 Hz. 
1/3 
1/2 
1/2 
1/2 
1/2 
1/2 
1/2 
 
Motor 
Amps 
8 10 10 10 10 10 10 
Height 
to 
Outlet 
65 65 73 73 73 73 73 
Height 
to 
Inlet 
28 28 36 36 36 36 36 
 
Approx. Shipping Weight - lbs 
1470 
1520 
1600 
1710 
1870 
2000 
2120 
Recoveries based on 83% thermal efficiency. ASHRAE 90.1 compliant. 
Dimensions are in inches unless otherwise specified. 
For standard and optional equipment, see form # PV 6293. 
 
 
 
 
STANDARD ELECTRICAL REQUIREMENTS: 
CONTROL VOLTAGE:  120V, 1Ø, 60 HZ., 2 AMPS 
MOTOR VOLTAGE: 120V, 1Ø, 60 HZ. 
SEE ABOVE CHART FOR BLOWER MOTOR AMPS 
 
 
 
VENTING REQUIREMENTS: 
-.02" TO -.06" W.C. (NEGATIVE PRESSURE). 
THE ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED UPON THE 
VENT CONNECTION DIAMETER EXCLUSIVELY. 
FOR PROPER SIZING, CONSULT VENTING SUPPLIER. 
 
 
1. Control Enclosure 
2. ASME Temperature & 
  Pressure Relief Valve 
3. 3” NPT Handhole
PVI RESERVES THE RIGHT TO CHANGE THE DESIGN AND 
SPECIFICATION WITHOUT NOTICE.