especially important in areas where painting, plastering, or
spraying of fireproof material, etc. is not yet complete. Foreign
material that is allowed to accumulate within the units can pre-
vent proper start-up and necessitate costly clean-up operations.
Before installing any of the system components, be sure to
examine each pipe, fitting, and valve, and remove any dirt or
foreign material found in or on these components.
INSPECT UNIT — To prepare the unit for installation, com-
plete the procedures listed below:
1. Compare the electrical data on the unit nameplate with
ordering and shipping information to verify that the
correct unit has been shipped.
2. Do not remove the packaging until the unit is ready for
installation.
3. Verify that the unit’s refrigerant tubing is free of kinks or
dents, and that it does not touch other unit components.
4. Inspect all electrical connections. Be sure connections are
clean and tight at their terminations. 
5. Loosen compressor bolts until the compressor rides freely
on springs. Remove shipping restraints.
6. Remove the four 6 mm (
1
/
4
 in.) shipping bolts from com-
pressor support plate (two bolts on each side) to maxi-
mize vibration and sound alternation.
7. Remove any blower support cardboard from inlet of the
blower.
8. Locate and verify any accessory kit located in compressor
and/or blower section.
9. Remove any access panel screws that may be difficult to
remove once unit is installed.
Table 1 — Physical Data — 50HQP072-120 Units
*All units have grommet and spring compressor mountings, and
2.2 mm and 3.5 mm electrical knockouts.
†51 mm filters are available as field-installed accessory.
NOTE: Use the lowest maximum pressure rating when multiple
options are combined:
CAUTION
DO NOT store or install units in corrosive environments or
in locations subject to temperature or humidity extremes
(e.g., attics, garages, rooftops, etc.). Corrosive conditions
and high temperature or humidity can significantly reduce
performance, reliability, and service life. Always move
units in an upright position. Tilting units on their sides may
cause equipment damage.
CAUTION
Failure to remove shipping brackets from spring-mounted
compressors will cause excessive noise and could cause
component failure due to added vibration.
UNIT 50HQP
072
096
120
COMPRESSOR QUANTITY*
Scroll
   Number of Circuits (Compressors)
2
   Factory Charge HFC-410A (kg) per circuit
1.70
2.15
2.27
BLOWER MOTOR
   Blower Motor Quantity
1
   Standard Motor (kW)
0.75
1.49
2.24
BLOWER
   No. of Blowers
1
   Blower Wheel Size D x W (cm)
30.48 x 30.48
WATER CONNECTION SIZE
   FPT (in.) [mm]
1
1
/
4
 [31.8]
1
1
/
2
 [38.1]
COAX VOLUME
   Volume (liters)
6.13
6.85
9.08
CONDENSATE CONNECTION SIZE
   FPT (in.) [mm] 
 
3
/
4
 [19.1]
AIR COIL DATA
   Air Coil Dimensions H x W (cm)
50.8 x 137.16
50.8 x 162.56
   Air Coil Total Face Area (sq m) 
0.70
0.83
   Air Coil Tube Size (cm)
0.953
   Air Coil Fin Spacing (fins per cm)
5.5
   Air Coil Number of Rows
3
MISCELLANEOUS DATA
   Filter Standard - Throwaway (qty) (cm)†
40.64 x 50.80 x 2.54
   Weight - Operating (kg)
265.8
292.1
316.6
   Weight - Packaged (kg)
283.9
310.3
334.8
OPTION
MAXIMUM PRESSURE (kPa)
Base Unit
3100