FX2N-8AD Analog input block
Buffer Memory (BFM) 8
8-23
8.2.11
BFM #28: Scale over status
When the analog input value of each channel is outside the range in which A/D conversion is
available, the result is written to BFM #28.
Once a bit turns ON, it remains ON until it is overwritten with the OFF status by the TO
instruction given by the PLC main unit or the power is turned off.
Even while a scale over error is detected, the data (BFM #10 to BFM #17) of each channel is
continuously updated.
Table 8.4: Range in which A/D conversion is available
Voltage input 
mode
Current input 
mode
Thermocouple input mode
K type
J type
T type
- 10.240V to 
10.235V
- 20.480mA to 
20.470mA
-100 
°
C to 1200 
°
C
-148 
°
F to 2192 
°
F
-100 
°
C to 600 
°
C
-148 
°
F to 1112 
°
F
-100 
°
C to 350 
°
C
-148 
°
F to 662 
°
F