 Control Circuit Terminals 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Terminal
name 
Description 
Ratings and Notes 
P24 
+24V power for 
inputs 
24VDC supply, 100 mA max. 
CM1 
+24V common 
Common for 24V supply, FW, 
TH, inputs 1 to 5, and FM.  
(Note: Do not ground) 
PLC 
Common for logic 
inputs 
Common for input terminals 1 
to 5, jumper to CM1 for sinking, 
jumper to P24 for sourcing 
1, 2, 3, 
4, 5 
Intelligent 
(programmable) 
discrete logic 
inputs 
FW Forward/stop 
command 
27VDC max. (use P24 or an  
external supply referenced to  
terminal CM1), 4,7k
ȍ input 
impedance 
11C-11A 
12C-12A
Intelligent 
(programmable) 
relay outputs 
Normally open contacts 
250VAC / 30VDC, 5A (resistive 
load) max., 250VAC / 30VDC, 
5A (inductive load) max. 
Minimum load 5VDC, 5mA 
TH 
Thermistor input 
Reference to CM1, min. 
thermistor power 100mW 
FM 
PWM output 
0 to 10VDC, 1.2 mA max.,   
50% duty cycle