“C” Group: Intelligent Terminal Functions
Configur
ing
Dr
iv
e P
a
ra
m
e
ters
3–36
Output Terminal Configuration
The inverter provides configuration for logic (discrete) and analog outputs, shown in the 
table below.
The output logic convention is programmable for terminals [11] and [12]. The open-
collector output terminals [11] and [12] default to normally open (active low), but you 
can select normally closed (active high) for these terminals in order to invert the sense of 
the logic. You can invert the logical sense of the alarm relay output as well.
“C” Function
Run 
Mode 
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FE 
(CE)
–FU 
(UL)
–FR 
(Jpn)
Units
C_21 Terminal [11] function
Select function for terminal 
[11], 6 options (see next 
section)
01
[FA1]
01
[FA1]
01
[FA1]
OUT-TM 1     FA1
C_22 Terminal [12] function
Select function f or terminal 
[12], 6 options (see next 
section)
00
[RUN]
00
[RUN]
00
[RUN]
OUT-TM 2     RUN
C_23 [FM] signal selection
Select function for terminal 
[FM], 3 options (see next 
section)
00
[A–F]
00
[A–F]
00
[A–F]
MONITOR      A-F
“C” Function
Run 
Mode 
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FE 
(CE)
–FU 
(UL)
–FR 
(Jpn)
Units
C_31 Terminal [11] active 
state (–FU)
Select logic convention, two 
option codes:
00 ...normally open [NO]
01 ...normally closed [NC]
00
OUT-TM O/C-1  NO
Reserved (–FE / –FR)
(reserved) DO NOT EDIT
00
00
(not displayed)
C_32 Terminal [12] active 
state (–FU)
Select logic convention, two 
option codes:
00 ...normally open [NO]
01 ...normally closed [NC]
00
OUT-TM O/C-2  NO
Terminal [11] active 
state (–FE / –FR)
(reserved) DO NOT EDIT
00
00
OUT-TM O/C-1  NO
C_33 Alarm relay active state
Select logic convention, two 
option codes:
00 ...normally open [NO]
01 ...normally closed [NC]
01
01
01
OUT-TM O/C-RY NO