Using Intelligent Input Terminals
Oper
ations
and Monitor
ing
4–14
Free-run Stop
When the terminal [FRS] is turned ON, the inverter stops the output and the motor enters 
the free-run state (coasting). If terminal [FRS] is turned OFF, the output resumes sending 
power to the motor if the Run command is still active. The free-run stop feature works 
with other parameters to provide flexibility in stopping and starting motor rotation.
In the figure below, parameter B_88 selects whether the inverter resumes operation from 
0 Hz (left graph) or the current motor rotation speed (right graph) when the [FRS] 
terminal turns OFF. The application determines the best setting.
Parameter B_03 specifies a delay time before resuming operation from a free-run stop. 
To disable this feature, use a zero delay time.
Motor 
speed
[FW], 
[RV] 
Zero-frequency start
Motor 
speed
Resume from motor speed
wait time
B 03
B_88 = 00
B_88 = 01
1
0
t
t
FRS
FRS
[FW], 
[RV] 
1
0
1
0
1
0
Option
Code
Terminal 
Symbol
Function Name
Input 
State
Description
11
FRS
Free-run Stop
ON
Causes output to turn OFF, allowing motor to 
free run (coast) to stop
OFF
Output operates normally, so controlled deceler-
ation stops motor
Valid for inputs:
C_01, C_02, C_03, C_04, 
C_05
Required settings:
B_03, B_88, C_11 to C_15
Notes:
When you want the [FRS] terminal to be active low 
(normally closed logic), change the setting (C_11 to 
C_15) that corresponds to the input (C_01 to C_05) 
that is assigned the [FRS] function.
Example (requires input configuration—
see page 
):
See I/O specs on page 
1
2
3
4
5
L
P24
FRS